4.5 MAG 5000/6000 CT

4.5
MAG 5000/6000 CT
28
www.eltra-trade.com
8. Tighten cable glands to obtain optimum sealing.
CAUTION
When remote mounted, power supply PE wire must be connected to PE terminal (
Coil cable shield must be connected to SHIELD terminal.
9. Mount transmitter on terminal box.
10. Transmitter is ready to be powered up.
NOTICE
Exposing the transmitter to direct sunlight may increase the operating temperature
above its specified limit, and decrease display visibility.
A sun shield is available as accessory.
To ensure that the settings of this custody transfer-approved MAG 5000/6000 CT transmitter
are not changed, it is necessary to install a hardware key to lock the software functions and
to seal the device.
MAG 6000 CT is installed like a Standard MAG 6000 except for the final sealing.
Calibration sealing has been carried out at calibration.