SITRANS F M MAGFLO
2.
Installation
2.1 Installation of
transmitter MAG
6000
Safe area only!
2.2 Installation of sensor
Hazardous area
4
2. Installation
SFIDK.PS.026.C2.02
Transmitter MAG 6000 can be installed in the
safe area only!
Category 2 equipment
Sensors may be installed in zone 1 and zone 2.
The sensor must always be completely full with
liquid.
Therefore avoid:
• Installation at the highest point in the pipe
system
• Installation in vertical pipes with free outlet
For partially filled pipes or pipes with down-
ward flow and free outlet the flowmeter should
be located in a U-tube.
Installation in vertical pipes
Recommended flow direction: upwards. This
minimizes the effect on the measurement of
any gas/air bubbles in the liquid.