Siemens Albatros 2 RVS13 Series User Manual page 96

Boiler controllers
Table of Contents

Advertisement

Interfaces
Degree of protection
Directives and
Standards
Climatic conditions
Weight
96/109
Siemens
Building Technologies
BSB
Max. cable length
Basic unit – peripheral device
Max. total length
Min. cross-sectional area
Protection class
Protection degree of housing
Degree of pollution
Product standard
Electromagnetic compatibility
(Applications)
EU Conformity (CE)
Environmental compatibility
Storage to EN 60721-3-1
Transport to EN 60721-3-2
Operation to EN 60721-3-3
Weight (excl. packaging)
User Manual
8 Technical data
2-wire connection, not interchangeable
200 m
400 m (max. cable capacitance) 60 nF)
2
0.5 mm
If correctly installed, low-voltage live parts
meet the requirements of safety class II
according to EN 60730-1
IP00 according to EN 60529
2 according to EN 60730-1
EN 60730-1
Automatic electrical controls for household
and similar use
For use in residential, commerce, light-
industrial and industrial environments
CE1T2357xx01
The product environmental declaration
CE1E2357en03 contains data on
environmentally compatible product design
and assessments (RoHS compliance,
materials composition, packaging,
environmental benefit, disposal).
class 1K3, temperature -20...65°C
class 2K3, temperature -25...70 °C
class 3K5, temperature 0...50 °C
(noncondensing)
RVS13.123: 566 g
RVS13.143: 566 g
RVS53.183: 776 g
CE1U2357en
2014-07-30