Mounting notes

Mounting method

Connections

Mains
Connection to basic unit
Siemens
Building Technologies
3.7.5

Checking the wireless components

To check whether the connections to the required system components are operational,
consult operating lines 130 through 135 on operating page "Wireless" (operating level
"Commissioning").

3.8 Power supply AVS16.290

The boiler control panel is designed for installation in floor-standing or wall-hung oil or
gas boilers and may only be used for that purpose. For installation, the following points
must be observed:
· Power to the control panel may be supplied only after it is completely fitted in the cut-
out. Extension modules or dummy covers for which cutouts are provided must also
be fitted beforehand
· Dimensions of cutout 92 x 92 mm, sheet metal thickness 0.5 to 3.0 mm
· The boiler control panel must be secured with the 4 clips provided on the panel
· Power to the control panel may be supplied only after it is completely fitted in the cut-
out. Extensions or dummy covers for which cutouts are provided must also be fitted
beforehand
· Control panel wiring to the connection terminals does not feature strain relief so that
the cables must be secured inside the boiler
· The local regulations for electrical installation must be complied with.
installation
Terminal
Marking
L
Phase AC 230 V
Protective earth
N
Neutral conductor
Terminal
Marking
1
L
2
3
N
4
4
5
5
User Manual
3 Mounting and installation
Phase AC 230 V basic unit
Protective earth
Neutral conductor
Phase AC 230 V burner
Input burner fault
Removal
Leiterfarben
Blue
Geen + yellow
Blue
Leiterfarben
Brown
Geen + yellow
Blue
Black
-
29/109
CE1U2357en
2014-07-30