Johnson Controls CKM-MR51E Hardware Installation Manual

Reader terminal module

Advertisement

P2000
Security Management System
hardware
installation
CKM-MR51E
authentic Mercury™ PoE module
24-10707-58 Revision E
December 2017

Advertisement

loading

Summary of Contents for Johnson Controls CKM-MR51E

  • Page 1 P2000 Security Management System hardware installation CKM-MR51E authentic Mercury™ PoE module 24-10707-58 Revision E December 2017...
  • Page 2 If this document is translated from the original English version by Johnson Controls, all reasonable endeavors will be used to ensure the accuracy of translation. Johnson Controls shall not be liable for any translation errors contained herein or for incidental or consequential damages in connection with the furnishing or use of this translated material.
  • Page 3 Declarations of Conformity United States: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
  • Page 4 CKM-MR51E When installed at the site the following requirements must be met to comply with these standards. 1. The CKM-MR51E shall be mounted in Listed Enclosures CKM-CE75-E1M, CKM-CE75- E2M, CKM-CE150-E4M, and Listed Burglar Alarm and Access Control System Units SPE10000-1H00, SPH10000-1H00, SPF10000-1I00, SPF1I100-1I00 or SPF1I300-1J00.
  • Page 5: Table Of Contents

    UL 294 listed, power limited source (12 VDC). One physical barrier can be controlled with the CKM-MR51E, using single or paired readers. The first reader port can accommodate a read head that utilizes Wiegand, magnetic stripe, or two-wire RS-485 electrical signaling standards;...
  • Page 6: Mounting Information

    CKM-MR51E Hardware Installation Manual 24-10707-58 Rev. E A mounting plate is supplied with the unit. The CKM-MR51E may be mounted in an enclosure; the supplied mounting plate has mounting holes that match the CKM-MR50 mounting footprint. OUNTING NFORMATION VO LED BZR CLK DAT GND...
  • Page 7 TAMPER SWITCH MR51e WITH INCLUDED MOUNTING PLATE OPTIONAL 3-GANG JUNCTION BOX TO ETHERNET FIELD WIRING NETWORK Figure 3: CKM-MR51E Mounting Side View Figure 4 shows mounting plate dimensions. Ø0.16 [Ø4.0] Ø0.16 [Ø4.0] 3-GANG MGT HOLES MR50 MGT HOLES 2.35 [59.7] 3.30 [83.8]...
  • Page 8: Wiring Information

    Cabling should be made using good wiring practices and should be long enough to allow service loops at their terminations in the enclosure. Input Power The CKM-MR51E is powered by one of two ways (jumper selected): • Power is supplied via the Ethernet connection using PoE, fully compliant to IEEE 802.3af, or...
  • Page 9 Figure 5: CKM-MR51E First Reader Wiring Figure 6: CKM-MR51E Second Reader Wiring : When powering any remote device(s) by the CKM-MR51E, care MPORTANT must be taken not to exceed the maximum current available. Cable gauge must also be evaluated. See Specifications for details.
  • Page 10 Figure 7 are supported, but may not be typical. Standard Supervised Circuit, 1K,1% Normally Open Contact 1K,1% Standard Supervised Circuit, 1K,1% Normally Closed Contact 1K,1% Unsupervised Circuit, Normally Closed Contact Unsupervised Circuit, Normally Open Contact Figure 7: CKM-MR51E Input Circuit Wiring...
  • Page 11: Setup Information

    MOV (metal oxide varistor) be used to protect the relay. Wire should be of sufficient gauge to avoid voltage loss. : It is possible for the CKM-MR51E to provide power for a 12 VDC MPORTANT door strike providing the maximum current is not exceeded;...
  • Page 12 CKM-MR51E Hardware Installation Manual 24-10707-58 Rev. E Table 1: Connections Connection Symbol Description TB1-1 Input 1 TB1-2 TB1-3 Input 2 TB1-4 TB2-1 Input 3 TB2-2 TB2-3 Input 4 TB2-4 TB3-1 Reader 1 Power Output – 12 VDC TB3-2 Reader 1 LED Output...
  • Page 13: Ip Address Configuration

    MSC-Specific DHCP (original method) Public DHCP Static IP Programming mode for static IP address assignment MSC-Specific DHCP (original method). 1. Public DHCP and Static IP Addressing Modes are available with CKM-MR51E firmware revisions 1.4.2 and later. IP A DDRESS ONFIGURATION The CKM-MR51E module uses two addressing modes: static IP addresses or public DHCP.
  • Page 14 Use straight-through Ethernet cable if connecting via a hub/switch. To enable the module’s programming mode: 1. At the CKM-MR51E, set the DIP switches to “0011,” which is the programming mode for static IP addressing (see Table To configure the static IP address: 1.
  • Page 15 6. Click Assign Static Address. To use the static IP address: 1. At the CKM-MR51E, set the DIP switches to “0010,” which is the Static IP mode (see Table 2. Press S2 (the reset switch) to reset the board.
  • Page 16: Status Leds

    1. If this input is defined, every 3 seconds the LED is pulsed to its opposite state for 0.1 second, otherwise the LED is off. After the CKM-MR51E has received its IP address, the following table describes the LEDs in the normal running mode. If the communication is lost, the CKM-MR51E reverts back to the “waiting for IP address”...
  • Page 17: Specifications

    CKM-MR51E Hardware Installation Manual 24-10707-58 Rev. E PECIFICATIONS Use this interface in low voltage, Class 2 circuits only. Table 6: CKM-MR51E Specifications Category Description Power Input PoE Power Input 12.95 W, compliant to IEEE 802.3af, or 12 VDC 10%, 900 mA maximum...
  • Page 18: Maintenance

    CKM-MR51E Hardware Installation Manual 24-10707-58 Rev. E AINTENANCE Impaired Performance The following is a list of the impaired performance conditions: • Unit environment not as specified • Unit power not as specified • Cable type and length not as specified...