Model CV-300B Grooved End
Swing Check Valves
General
Description
The TYCO Model CV-300B Grooved
End Swing Check Valves are compact
and rugged swing-type units that
allow water flow in one direction and
prevent flow in the opposite direction.
A resilient elastomer seal facing on the
spring-loaded clapper ensures a leak-
tight seal and non-sticking operation.
The Model CV-300B Check Valves are
designed to minimize water hammer
caused by flow reversal.
The Model CV-300B Grooved End
Swing Check Valves are furnished with
grooved ends and can be installed
using GRINNELL Grooved Couplings
or GRINNELL Figure 71 Flange Adapt-
ers. These valves can be installed hori-
zontally, or vertically with the flow in the
upward direction (Ref. Figure 2).
NOTICE
The TYCO Model CV-300B Grooved
End Swing Check Valves described
herein must be installed and main-
tained in compliance with this docu-
ment and with the applicable standards
of the NATIONAL FIRE PROTECTION
ASSOCIATION (NFPA), in addition to
the standards
of any authorities having
jurisdiction. Failure to do so may impair
the performance of these devices.
Never remove any piping component
nor correct or modify any piping defi-
ciencies without first de-pressurizing
and draining the system. Failure to do
so may result in serious personal injury,
property damage, and/or impaired
device performance.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Page 1 of 2
Technical
Data
Approvals
UL and ULC Listed
FM Approved
Sizes
4 in. (DN100)
Maximum Working Pressure
300 psi (20,7 bar)
Valve Assembly Finish
Red,
non-lead paint
Weight
19.84 lbs (9 kg)
Installation
The Model CV-300B Grooved End
Swing Check Valves are to be installed
in accordance with this section:
Step 1. The arrow cast on the body
must point in the direction of the flow
(Ref. Figure 2):
Vertical installation - orient the valve
with the flow arrow pointed up
Horizontal installation - orient the
valve with the large boss facing
either up or down, and the flow arrow
pointed left or right
Step 2. Grooved end pipe couplings
used with the Model CV-300B Grooved
End Swing Check Valves must be
installed in accordance with manufac-
turer's instructions.
Note: Valves should be installed a rea-
sonable distance downstream from
pumps, elbows, expanders, reducers,
or other similar devices to extend the
valve life. Standard piping practices call
for a minimum of five (5) times the pipe
diameter for general use.
Care and
Maintenance
The TYCO Model CV-300B Grooved
End Swing Check Valves must be main-
tained and serviced in accordance with
this section.
AUGUST 2018
Worldwide
www.tyco-fire.com
Contacts
For fire protection pressure rating,
listing and approval information, contact
your TYCO representative.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
system from the proper authorities
and notify all personnel who may be
affected by this decision.
After placing a fire protection system
in service, notify the proper authorities
and advise those responsible for moni-
toring proprietary and/or central station
alarms.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the NATIONAL FIRE PROTECTION
ASSOCIATION (e.g., NFPA 25), in addi-
tion to the standards of any authority
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions. Any impairments
must be immediately corrected.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
TFP1552

Advertisement

loading

Summary of Contents for Johnson Controls Tyco CV-300B

  • Page 1 Worldwide www.tyco-fire.com Contacts Model CV-300B Grooved End Swing Check Valves General Technical Description Data The TYCO Model CV-300B Grooved Approvals End Swing Check Valves are compact UL and ULC Listed and rugged swing-type units that FM Approved allow water flow in one direction and Sizes prevent flow in the opposite direction.
  • Page 2 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700 © 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association...