29. TECHNICAL DATA

29.1. AS302P Meter

Current:
IEC Ratings
MID/EN Rating
Frequency
Reference Voltage
Voltage Operating Range
Short Circuit Current
Insulation Voltage
Impulse Withstand
- Live to Neutral
- Live and Auxiliary Outputs
Power Consumption
(At reference conditions and stated current)
Voltage Circuit
Current Circuit @ Basic Current
Display
Viewing Angles
Meter Constant (pulsing LED output)
Pulse Width
Auxiliary Relay
Product Design Life
Service Design Life
Temperature
Humidity
Dimensions
Accuracy Class kWh
Case
Terminals Main
© Honeywell - M450 001 1D - 23.05.2019
Operating & Maintenance Instructions
Ib - Imax = 5 - 100A, 10 - 100A, 20 - 100A
Imin - Itr(Imax) = 1.0 - 20(100)A, 0.5 10(100)A, 0.25 - 5(100)A
50 Hz
230V a.c.
±20%
Short Circuit Current Withstand: 30 Imax
4000 Vac 1 min
12kV (40 ohm source)
6kV (40 ohm source)
Max 0.8W
Average < 4W under normal operating conditions
0,02VA
High Contrast, 2 Line Display
- 10˚ above, 40˚ below the horizontal
Vertical
- 30˚ either side of vertical
Horizontal
4000 Pulses/kWh (kvarh)
Wavelength 640nm
5 ms
230V, 2A, a.c.
20 years
15 years
Specified Operational Range:
Limit Operating Range:
Storage Range:
Non - Condensing
Annual Mean 75% (95% for 30 days spread over one year)
125mm (H) x 130mm (W) x 65mm (D)
EC Directive 2014/22/EC (MID) - Class A or Class B. (EN 504703)
IEC 62053-21, Class 1 or Class 2
BS 7856:2013
IP53 to IEC 60529:1989
8.2mm Diameter Bore, 2 x M6 Combi Pinch Screws
(Screw Material - Steel, Coated with Zinc Chromate)
Max Torque 2.8 N m
-25 C to +55C
-25 C to +70C
-25 C to +70C
47