Positioning Of The Ignition And Flame Sensing Electrode; Check Of Combustion Parameters - Baxi 45 HTE Installation, Operation And Maintenance Manual

Floor standing condensing gas boilers
Table of Contents

Advertisement

Available languages

Available languages

16. positioning of the ignition and flame sensing electrode

Figure 14

17. check of combustion parameters

Drill a hole in the flue at a distance from the boiler equivalent to twice the diameter of the flue to measure
combustion efficiency and combustion flue composition in accordance with the rules in force. Use this hole to
measure the following parameters:
• Combustion flue temperature
• Ox­ygen (O
) or carbon diox­ide (CO
2
• Carbon monox­ide (CO) concentration.
Measure the temperature of combustion air near the air inlet to the boiler. The necessary hole must be made by
the technician responsible for the heating system when the system is first started up, and must then be closed
to ensure that the flue remains properly sealed during normal operation.
Important! Close the flue test point
hole on completion of measurements.
Figure 15
IstructIons pErtaInIng to thE InstallEr
) concentration.
2
LOCATION OF FLUE TEST
POINT HOLE
BOILER FLUE TEST
POINT HOLE
71
912.359.1 - IE

Advertisement

Table of Contents
loading

This manual is also suitable for:

65 hte

Table of Contents