To facilitate measurement of the combustion efficiency and improve the cleanliness of the production products,
the chimney sweep function can be activated by proceeding as described below:
1) press the
(2-3) together until the pointer " " appears on the display alongside the
seconds but no more than 6 seconds). In these conditions, the boiler operates at the max­imum heat output
in central heating mode.
2) press either of the
Figure 16
To ensure the boiler operates at peak efficiency, the following checks must be performed every year:
• check on the appearance and tightness of the gas and combustion circuit gaskets;
• check on the condition and position of the ignition and flame sensing electrodes (see section 16);
• check on the condition of the burner and its fix­ing to the aluminium flange;
• check for any dirt in the combustion chamber. Use a vacuum-cleaner for this cleaning operation;
• check that the gas valve is calibrated correctly (see section 13);
• check that there is no dirt in the siphon;
• check on the central heating system pressure;
• check on the ex­pansion vessel pressure.