22. ElECtROnIC BOaRd CalIBRatIOn

When the jumper or the switch is in the oFF position
(fig. 15a):
Met
operation of the boiler with NATURAL gas
t.risc
boiler heating temperature range 30 - 85°c
t-off
150-seconds heating stand-by time
When the jumper or the switch is in the on position
(fig. 15b):
GpL
operation of the boiler with LPG
t.risc
boiler heating temperature range 30 - 45°c
t-off
30-seconds heating stand-by time
nB.
make sure that electrical power supply has been disconnected before making settings.

23. pOSItIOnInG Of tHE IGnItIOn and flaME SEnSInG ElECtROdE

Figure 16

24. CHECk Of COMBUStIOn paRaMEtERS

The boiler has two connection points specifically designed to allow technicians to measure the combustion efficiency after
installation and ensure that the combustion products do not constitute a health risk.
One connection point is connected to the flue gas discharge circuit, and allows monitoring of the quality of the combustion
products and the combustion efficiency.
The other is connected to the combustion air intake circuit, allowing checking of any recycling of the combustion products
in case of coaxial pipelines.
The following parameters can be measured at the connection point on the flue gas circuit:
• temperature of the combustion products;
• oxygen (O
) or carbon dioxide (CO
2
• carbon monoxide (CO) concentration.
The combustion air temperature must be measured at the connection point on the air intake circuit, inserting the measurement
probe to a depth of about 3 cm.
The boiler has two connection points specifically designed to allow technicians to measure the combustion efficiency after
installation and ensure that the combustion products do not constitute a health risk.
One connection point is connected to the flue gas discharge circuit, and allows monitoring of the quality of the combustion
products and the combustion efficiency.
The other is connected to the combustion air intake circuit, allowing checking of any recycling of the combustion products
in case of coaxial pipelines.
instructions pertaininG to the
Figure 15a
Figure 15b
) concentration;
2
instaLLer
18
924.674.3 - GB