Positioning Of The Ignition And Flame Sensing Electrode; Check Of Combustion Parameters; Activating The Flue-Sweeper Function - Baxi Luna HT Installers And Users Instructions

Wall-mounted condensing boilers
Table of Contents

Advertisement

19. Positioning of the ignition
and flame sensing electrode
20. Check of combustion
parameters
21. Activating the flue-sweeper
function
Figure 16
To measure combustion performance and hygiene levels of combustion products, the forced draught
boiler models are equipped with two test points on the tapered coupling specifically designed for this
purpose.
One of the two test points is connected to the exhaust flue duct to allow measurements of the combustion
products hygienic standards and combustion efficiency.
The second test point is connected to the comburant air inlet duct to check possible combustion
products circulation in case of coaxial ducts.
The exhaust flue duct test point allows measurements of the following:
• combustion products temperature;
• concentration of oxygen (O
• concentration of carbon monoxyde (CO).
The comburant air temperature must be measured at the test point connected to the air inlet duct.
Figure 17
To facilitate measurement of the combustion efficiency and improve the cleanliness of the production
products, the flue-sweeper function can be activated by proceeding as described below:
1) press the
(2-3) together until the pointer " " appears on the display alongside the
(about 3 seconds but no more than 6 seconds). In these conditions, the boiler operates at the
maximum heat output set for central heating.
2) press either of the
) or, alternatively, of carbon dioxyde (CO
2
flue gas
buttons to exit the function
28
);
2
combustion air
gasket
symbol