3.3
Power Supply Specifications
Item
Input power supply voltage
Power consumption
Power consumption (At
backlight off)
Inrush current
Permissible instantaneous
power failure time
Noise immunity
Dielectric withstand voltage
Insulation resistance
Operation at momentary power failure
The GOT continues to operate even upon 5ms or shorter instantaneous power failure.
The GOT stops operating if there is extended power failure or voltage drop, while it automatically resumes
operation as soon as the power is restored.
3 SPECIFICATIONS
30
3.3 Power Supply Specifications
Specifications
GS2110-WTBD-N
GS2107-WTBD-N
24VDC (+10% -15%), ripple voltage 200mV or less
7.6W (317mA/24V) or less
6.5W (271mA/24V) or less
3.8W (158mA/24V) or less
3.8W (158mA/24V) or less
17A or less (6ms, 25°C, at the maximum load)
Within 5ms
Conforms to IEC61000-4-4, 2kV (power supply line)
350VAC for 1 minute (across power supply terminals and earth)
500VDC across power terminals and earth, 10 MΩ or more by an insulation resistance tester
GS2110-WTBD
GS2107-WTBD
7.6W (317mA/24V) or less
6.5W (271mA/24V) or less
3.8W (158mA/24V) or less
3.8W (158mA/24V) or less