For Super-Slim Cassette Type; For Other Errors - York YEFE BZTM-MOW1 Series Service Manual

Pac fixed speed r410a 60hz cooling only
Table of Contents

Advertisement

For Super-slim cassette type:

Operation
Timer
Defrosting
lamp
lamp
OFF
fl fl F lash
Flash
OFF
OFF
OFF
Flash
Flash
OFF
OFF
Flash
Flash
Flash
OFF
Flash
OFF
OFF
Flash
OFF
ON

For other errors:

The display board may show a garbled code or a code undefined by the service manual. Ensure that this code is not a
temperature reading.
Troubleshooting:
Test the unit using the remote control. If the unit does not respond to the remote, the indoor PCB requires replacement.
If the unit responds, the display board requires replacement.
Page 82
Alarm
Display
lamp
lamp
OFF
OFF
E2
OFF
OFF
E3
Flash
OFF
E4
OFF
OFF
E7
OFF
Flash
E8
Flash
OFF
Ed
OFF
Flash
EC
Flash
Flash
F0
Flash
Flash
F1
Flash
Flash
F2
Error Information
Indoor room temperature sensor T1 is in open
circuit or has short circuited
Evaporator coil temperature sensor T2 is in
open circuit or has short circuited
Condenser coil temperature sensor T3 is in
open circuit or has short circuited (except for
18k/24k/36k cooling-only models)
Indoor unit EEPROM parameter error
Water level alarm malfunction
Protection of Low pressure (only for 48k
and 60k models)
Refrigerant leakage detection
Communication malfunction between main
PCB and up-down panel PCB
Up-down panel malfunction
Up-down panel is not closed
Solution
Page 96
Page 96
Page 96
Page 97
Page 98
Page 105
Page 99
Page 100
Page 101
-