Collecting The Refrigerant Into The Outdoor Unit; Indoor Unit - York YEFE BZTM-MOW1 Series Service Manual

Pac fixed speed r410a 60hz cooling only
Table of Contents

Advertisement

1.3.1

Indoor Unit

Collecting the refrigerant into the outdoor unit

Procedure:
1.
Confirm that the 2- and 3-way valves are opened.
2.
Connect the charge hose with the push pin of Handle
Lo to the 3-way valve's gas service port.
3.
Open the Handle Lo manifold valve to purge air
from the charge hose for 5 seconds and then close it
quickly.
4.
Close the 2-way valve.
5.
Operate the air conditioner in cooling mode. Cease
operations when the gauge reaches 0.1 MPa
(14.5 Psi).
6.
Close the 3-way valve so that the gauge rests
between 0.3 MPa (43.5 Psi) and 0.5 MPa (72.5 Psi).
7.
Disconnect the charge set and mount the caps of
service port and 2- and 3-way valves.
8.
Use a torque wrench to tighten the caps to a torque
of 18N.m.
9.
Check for gas leakage.
Air purging with vacuum pump
Page 25