Use the Up and Down buttons to change the temperature scale and press Mode to confirm
5.
the change.

Onboard temperature calibration

You can adjust the value of the displayed ambient temperature. To adjust the value, complete the
following steps:
1.
Press Mode to set the thermostat to OFF mode.
Press and hold Mode and Fan for 5 seconds to access the advanced settings menu.
2.
3.
Press Up to navigate to UP, then press Mode to enter the menu.
Press Mode to navigate to 02.
4.
5.
Use the Up and Down buttons to change the current temperature.
Press Mode to confirm the change.
6.
Result The thermostat calculates the difference between the current measured temperature
and the user set current temperature to determine the calibration offset. Calibration changes the
temperature as part of measurement and scaling. The thermostat uses the calibrated temperature
for temperature control.
The default calibration offset value is 0

Remote sensor temperature calibration

If you installed a remote sensor, you can adjust the value of the displayed remote sensor
temperature. To adjust the value, complete the following steps:
1.
Press Mode to set the thermostat to OFF mode.
2.
Press and hold Mode and Fan for 5 seconds to access the advanced settings menu.
3.
Press Up to navigate to UP, then press Mode to enter the menu.
Press Mode to navigate to 03.
4.
5.
Use the Up and Down buttons to change the current temperature.
Press Mode to confirm the change.
6.
Result The thermostat calculates the difference between the current measured temperature
and the user set current temperature to determine the calibration offset. Calibration changes the
temperature as part of measurement and scaling. The thermostat uses the calibrated temperature
for temperature control.
The default calibration offset value is 0.
Note: The remote sensor calibration menu option is visible only when the remote sensor
temperature reading is ready.

Pipe sensor temperature calibration

If you installed a pipe sensor, you can adjust the value of the displayed pipe sensor temperature. To
adjust the value, complete the following steps:
Press Mode to set the thermostat to OFF mode.
1.
2.
Press and hold Mode and Fan for 5 seconds to access the advanced settings menu.
Press Up to navigate to UP, then press Mode to enter the menu.
3.
4.
Press Mode to navigate to 04.
5.
Use the Up and Down buttons to change the current temperature.
22
FCP Non-Programmable and Programmable Fan Coil or PTAC Thermostat Largo User Guide