Honeywell Gamewell FCI S3 Series Manual page 47

Small addressable fire alarm control panel
Table of Contents

Advertisement

SLP Main Board Features
UL Standard Functions
Alarm Verification
Supervisory Signal Operation
Manual Release/Abort Switch Interaction No
NAC Reactivation (Alarm Resound)
S3 Series UL Listing Document — P/N LS10005-051GF-E:D3 3/09/2016
Yes, the S3 has Alarm Verification.
Refer to the UL Standard 864 9th Edition, Sections 55.2 to 55.28 .
Figure 4.1.1.1 illustrates the Alarm Verification Timing.
INITIAL
ALARM
DETECTION
A
Yes, the S3 has Two-Wire Compatibility.
Refer to the Compatibility Addendum for Gamewell-FCI Manuals,
P/N:9000-0427.
An indication when a product is intended to handle detectors with
optional features or a product is intended to handle more than one
detector in the alarm condition shall be included.
S3 Functionality:
Yes, the S3 is compatible with the following Two-Wire detectors:
- System Sensor devices (using the SLC-PM).
- Apollo devices (using the SLC95-PM).
Both SLC loops must be the same protocol.
A stipulation that detectors of different models are not to be mixed or
matched on a system, unless the system is specifically intended to be
installed in that configuration. When mixing is permitted, specific
limitations shall be included. This information can alternatively be
included in the Compatibility Section.
S3 Functionality:
For information on compatible detector models, refer to the
Compatibility Addendum for Gamewell-FCI Manuals,
P/N: 9000-0427.
Yes (Non-Latching, Supervisory)
For products whose operation provide the capability of selecting non
automatic distinctive restoration-to-normal supervisory signals
(locking in the Supervisory signals until manually reset). Include
instructions or details for selecting the respective operation.
S3 Functionality:
Supervisory Latching or Non-Latching input devices depend on the
assigned device type configured in the CAMWorks Configuration
Program.
Supervisory Non-Latching produces a supervisory off-normal
condition. Activates YELLOW "supervisory" LEDs, activates
supervisory general output list. Reports event via DACT, if configured
to do so. Activates supervisory contacts on panel.
Yes
When a system is intended to provide signaling service to two or more
physically separated buildings or zones, re-energization of the
notification appliance circuits only on a zone basis meets the intent of
the requirement. Provide specifics covering installation constraints so
that it shall be clearly detailed in the control unit installation wiring
diagram/instructions. Systems are also not prohibited from having
provision to automatically disable re-energizing alarm notification
circuits due to subsequent activation of other addressable smoke
detectors of the same type located in the same room or space as the
initial activated device. Detail specifics.
S3 Functionality:
Yes, the NAC Reactivation (Alarm Resound) is performed on a per-
region basis.
Table 4.1.1 SLP Main Board Functionality (Continued)
S3 Functionality
CONFIRMED ALARM OR NEW
ADVANCED DEVICE
VERIFICATION PERIOD
110 SECONDS
CONFIRMATION
RETARD
PERIOD
PERIOD
SYSTEM FULL ALARM
RESPONSE
NO
ALARM
20
40
60
20
90
SECONDS
SECONDS
Figure 4.1.1.1 Alarm Verification Timing
Functionality
ALARM DETECTION
AFTER THE END OF
VERIFICATION CYCLE
RE-STARTES THE
VERIFICATION CYCLE
80
100
120
47

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents