Honeywell Gamewell FCI S3 Series Manual page 12

Small addressable fire alarm control panel
Table of Contents

Advertisement

Installation Wiring
Designation
TB4-5
TB4-6
TB4-7
TB4-8
TB4-9
TB5-1
TB5-2
TB5-3
TB5-4
TB6-1
TB6-2
J1
J2
J4
J5
J6
J7
SW1-1
SW1-2
SW1-3
SW1-4
SW1-5
SW1-6
SW1-7
SW1-8
SW2
SW3
SW4
SW5
W1
W2
NOTE 1: When you use the output for Releasing, verify Jumper W1 and configure within
CAMWorks. Refer to Releasing in the General Settings Section for proper operation.
NOTE 2: The RS-232 printer port connection cannot exceed 20 ft.; it must be in conduit and in the
same room as the panel. The PRN-7 Printer is a dot-matrix printer. It is shipped with a DB-9
Adapter Kit that provides the necessary hardware and cables for installation. For additional
information on the PRN-7 Printer, refer to the Manufacturer's Installation Guide.
NOTE 3: When the Ethernet port is connected to FocalPoint, it cannot exceed 20 ft.; it must be in
conduit and in the same room as the panel.
NOTE 4: For Service Use Only.
Table 2.2.1.1 SLP-E3 Main Circuit Board Installation Wiring Terminals (Continued)
12
Description
SUPV NO
Supervisory relay contact normally OPEN N/O
SUPV C
Supervisory relay contact common
TRBL NC
Trouble relay contact normally CLOSED N/C
TRBL NO
Trouble relay contact normally OPEN N/C
TRBL C
Trouble relay contact common
RS-232 GND
For Programming, GND connects to red lead on the
download cable P/N 75267.
For Printer Port, GND connects to printer DB-9, PIN-5.
RS-232 TxD
For Programming, TxD connects to black lead on the
download cable P/N 75267.
For Printer Port, TxD connects to printer DB-9, PIN-2.
RS-232 Supervision Optional printer supervision.
For Printer Port, SUPV connects to printer DB-9, PIN-4.
RS-232 RxD
For Programming, RxD connects to green lead on the
download cable P/N 75267.
For Printer Port, RxD connects to printer DB-9, PIN-3.
BAT +
Positive power for battery connection
BAT -
Negative power for battery connection
AC SUPV / + 24
Power supply input connection
ETHERNET
RJ45 10/100 Ethernet connection for configuration downloading and /or
FocalPoint connection (See Note 3)
NETWORK
Connects to J10 of the RPT-E3-UTP
SLC-PM Loop 1
SLC-PM Card connection for Loop 1
SLC95-PM Loop 2 SLC95-PM Card connection for Loop 2
LOCAL DISPLAY
Local Display (LCD-SLP) connection. Connects to J5 of the LCD-SLP.
SLC 1 Disconnect
SLC1 disconnect (ON to disconnect, normally OFF) (See Note 4)
SLC 2 Disconnect
SLC2 disconnect (ON to disconnect, normally OFF) (See Note 4)
NAC 1-NAC 4
NAC1-NAC4 disconnect (ON to disconnect, normally OFF) (See Note 4)
Disconnect
Buzzer Disable
The main SLP-E3 Buzzer disable (ON to suppress local buzzer, normally
OFF on the SLP-E3) (See Note 4)
RS-232 BAUD Rate
RS-232 BAUD rate override (ON to force 115,200bps, OFF for configured
Configure
BAUD rate)
For Future Use
Reserved
For Future Use
Reserved
For Future Use
Reserved
RESET
System Reset button
SILENCE
System Silence button
ARLM ACK
System Alarm Acknowledge button
TRBL ACK
System Trouble Acknowledge button
MB/PR
"MB" = For Masterbox/Releasing Solenoid
"PR" = For Polarity Reversal (See Note 1)
AUX TERM
OFF (Normal RS485 operation)
ON (RS485 Termination)
S3 Series UL Listing Document — P/N LS10005-051GF-E:D3 3/09/2016
SLP-E3 Main Circuit Installation Wiring Diagram
Comments
NOTES
RS-232
Download or
Printer Port
(See Note 2)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents