6: Fml-E3 Installation Wiring Diagram; 7: Fml-E3 Installation Wiring Terminals - Honeywell Gamewell FCI S3 Series Manual

Small addressable fire alarm control panel
Table of Contents

Advertisement

Communication Circuits
2.10.6 FML-E3 Installation Wiring Diagram
The Fiber-Optic Multi-Mode (FML-E3) is an optional module that provides fiber connectivity to the network.
One FML-E3 is used per a network channel to transmit/receive. Figure 2.10.6.1 illustrates the FML-E3 circuit
board diagram. For system assembly and installation wiring terminal designations, refer to the FML-E3/FSL-
E3 Installation Instructions, P/N: LS10046-000GF-E. You can download this document from the Gamewell-
FCI Website (www.gamewell-fci.com).
2.10.7 FML-E3 Installation Wiring Terminals
Table 2.10.7.1 lists the FML-E3 installation wiring terminals.
Designation
J1
J2
SW1-1
SW1-2
SW1-3
SW1-4
P1
NOTE: Use standard ST connector fiber-optic cable, multi-mode, up to 200 µ (optimized for
62.5/125 µ). Signal loss up to 8dB maximum between nodes.
Table 2.10.7.2 lists the FML-E3 switch settings and drive currents.
NOTE: SW1-4 is not used.
S3 Series UL Listing Document — P/N LS10005-051GF-E:D3 3/09/2016
FML-E3
Figure 2.10.6.1 FML-E3 Circuit Board Diagram
Connects to the transmitting fiber. (See Note 1)
Connect to the receiving fiber. (See Note 1)
Sets the optical output power for the transmitting fiber. (See Table 2.10.7.2)
Sets the optical output power for the transmitting fiber. (See Table 2.10.7.2)
Sets the optical output power for the transmitting fiber. (See Table 2.10.7.2)
Not used
Plugs on to J5 (Port 1) or J6 (Port 2) of the RPT-E3-UTP.
Table 2.10.7.1 FML-E3 Installation Wiring Terminals
SW1-1
SW1-2
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
ON
ON
Table 2.10.7.2 FML-E3 Switch Settings and Drive Currents
J2
J1
Description
SW1-3
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Installation Wiring
FIBER-IN
FIBER-OUT
Drive Current
10 mA
20 mA
32 mA
42 mA
54 mA
64 mA
76 mA
86 mA