Communication Specifications Of The Mitsubishi Inverter Protocol (Computer Link Communication) - Mitsubishi Electric 800 Series Instruction Manual

Rs-485 interface board, rs-485 communication terminals
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

4.4
Communication specifications of the Mitsubishi inverter protocol
(computer link communication)
• Parameter setting, monitoring, etc. can be performed using Mitsubishi inverter protocol
• To make communication between the personal computer and inverter, setting of the communication specifications
must be made to the inverter in advance.
Data communication cannot be made if the initial settings are not made or if there is any setting error.
Pr.
Pr.
Name
group
RS-485
331
N030
communication
station number
RS-485
332
N031
communication
speed
RS-485
N032
communication
data length
RS-485
N033
communication
stop bit length
RS-485
communication
333
stop bit length /
data length
32
PARAMETER
Initial
Setting
value
range
Specify the inverter station number.
0
0 to 31
Set the inverter station numbers when two or more inverters are connected

to one personal computer.
3, 6, 12, 24,
Set the communication speed.
48, 96, 192,
The setting value  100 equals the communication speed.
96
384, 576,
For example, if 192 is set, the communication speed is 19200 bps.
768, 1152
0
Data length 8 bits
0
1
Data length 7 bits
0
Stop bit length 1 bit
1
1
Stop bit length 2 bits
0
Stop bit length 1 bit
1
Stop bit length 2 bits
1
10
Stop bit length 1 bit
11
Stop bit length 2 bits
.
Description
Data length 8 bits
Data length 7 bits

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a8ers