Selection Of Command Source In Network Operation Mode (Pr.550); Selection Of The Command Source Of The Pu Operation Mode (Pr.551) - Mitsubishi Electric 800 Series Instruction Manual

Rs-485 interface board, rs-485 communication terminals
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

4.2.1

Selection of command source in Network operation mode (Pr.550)

• Either of the RS-485 terminals or the communication option can be specified for the command source in the Network
operation mode.
• For example, whether or not the communication option is mounted, set Pr.550 ="1" to write parameters from or input the
start and frequency commands via RS-485 terminals in the Network operation mode.
NOTE
• In the initial setting, "9999" (communication option automatic recognition) is set for Pr.550. Thus, if the communication
option is mounted, parameters cannot be written or the start and frequency commands cannot be sent by
communications that use the RS-485 terminals. (Monitoring or parameter reading can be performed.)
4.2.2

Selection of the command source of the PU operation mode (Pr.551)

• Any of the PU connector, RS-485 terminals, or USB connector can be specified as the command source in the PU operation
mode.
• Set Pr.551 ="1" to use communication connected to the RS-485 terminals to write parameters or execute start and
frequency commands in the PU operation mode.
NOTE
• When Pr.550 ="1" (NET mode RS-485 terminals) and Pr.551 ="1" (PU mode RS-485 terminals), the PU operation
mode has a precedence. For this reason, if the communication option is not mounted, switching to the Network
operation mode is not longer possible.
21