Use - Siemens 7XV5662-0AB00 Manual

Communication converter s0-bus
Table of Contents

Advertisement

Available languages

Available languages

7XV5662-0AB00

Use

The Communication Converter (CC–S
device, which allows serial data exchange between two protection devices. A communicati-
on network is used for this purpose. The digital synchronous interfaces X.21 and G703–
64 kBit/s (G703.1) are used as ports.
On the opposite side a second CC–S
protection device (Figure 20). This conversion allows two protection devices to exchange
data with each other. With two CC–S
possible to send data from one protection device to a second device and to receive data from
there.
The connection to the protection device is made noise-proof via a fibre-optic link, the FO5
module. FO5 means that this is an optical 820–nm plug-in module in the protection device,
which carries out a clock recovery from the transmitting clock of the communcation network.
For more details, see SIPROTEC
The data transfer between the protection devices represents a point-to-point connection, it
is bit-transparent and synchronous.
The CC–S
supports simple commissioning of the entire communication path. It has a relay
0
contact to output a "device ready" signal (GOK / DR) and also has an extended range power
supply unit covering the entire normal DC and AC auxiliary voltage range. In addition, all
important operating states are signalled by LEDs.
RELAY 2
2x FO
FO5
2x FO
FO5
RELAY 3
2x FO
FO5
2x FO
FO5
Figure 20 Typical structure of a communication line
C53000-B1174-C151-1
0
converts the data back into data legible for the second
0
s and one communication connection, it is therefore
0
®
device manual.
1st Connection
KU-SO 2
FO 1
S0-Bus
B1
S0-Bus
B2
FO 2
KU-SO 3
FO 1
S0-Bus
B1
Channel B2
S0-Bus
B2
FO 2
2nd Connection
) is a peripheral device connected to the protection
ISDN
Channel B1
B1
S0-Bus
B2
RELAY 1
KU-SO 1
2x FO
FO 1
FO5
S0-Bus
2x FO
FO 1
FO5
English