Specification - Johnson Controls S300 Series Hardware Installation Manual

Hide thumbs Also See for S300 Series:
Table of Contents

Advertisement

S300-DIN-L
H
K
ARDWARE
IT
The Hardware Kit consists of:
Ground strap - The ground strap, used to provide ground to the enclosure door,
contains a ground strap with two ring terminals and two nuts. For an installation
procedure see page 3.
Self-tapping screws - On the backplate, there are two rows of holes along the long
edges of the plate. These are to be used with self-tapping screws. Use the
self-tapping screws to connect the aluminum shield of a shielded cable to the
backplate.
Snap-spade terminals - These terminals are used with S300-DIN-S enclosures only.
T
S
ECHNICAL
PECIFICATIONS
The enclosure and additional equipment described in this document have the following
specifications:
Model Number
Description
S300-DIN-L
Large enclosure
S300-DIN-L-PS
Power supply
S300-DIN-BRK
Battery bracket kit N/A
S300-BAT
Optional backup
battery
S300-DIN-PA1
Parts accessory
kit
24-10239-340 Rev. B
This document contains confidential and proprietary information of Johnson Controls
© 2017 Johnson Control

Specification

Made of 16 gauge steel with gray polyester powder
coating. 
Dimensions: 16x20x6.6 in (41x51x17 cm)
Approximate weight: fully loaded 45lb (20 kg)
24VDC out, 110/220VAC 50/60Hz in.
Input
AC nominal: 85-240Vac
Frequency: 47 – 63Hz 
Power rating: 220W
Output
Output voltage (nominal): 24VDC
Output current (continuous): 4.5A
Load regulation (no load to max.): ±0.25% typical
Other
Battery cutoff internal relay contacts: 15A
Battery PTC Circuit Breaker: 6A
12 volts, 7Ah battery. Two backup batteries are used
per enclosure to provide 24 VDC. Minimum one
hour sustained operation in S300-DIN-L at full load.
Dimensions: 5.94x3.7x2.56 in (15.1x9.4x6.5 cm)
Contains a DC power harness, a lock, a tamper
switch, and two spare connectors (3-position and
4-position).
Hardware Installation