York B1HH018 Installation Instructions Manual page 27

Champion series single package heat pumps
Hide thumbs Also See for B1HH018:
Table of Contents

Advertisement

66297-YIM-C-0205
TYPICAL WIRING DIAGRAM LEGEND (See page 24, 25 and 25)
TYPICAL WIRING DIAGRAM NOTES (See page 24, 25 and 25)
Unitary Products Group
CB
CIRCUIT BREAKER 24V, 3 AMP
CCH
CRANKCASE HEATER (OPTIONAL)
COMPR
COMPRESSOR
DS
DEFROST SENSOR, CLOSES @ 31˚F, OPENS @ 55˚F.
F1 F2 F3
FUSES, LINE VOLTAGE - 60 AMP (10, 15, 20 & 25 KW ELEC HEAT)
F4 F5 F6
FUSES, LINE VOLTAGE - 30 AMP (10, 15, 20 & 25 KW ELEC HEAT)
F7 F8 F9
FUSES, LINE VOLTAGE - 30 AMP (20, 25 KW ELEC HEAT)
F24
FUSE 24V SECONDARY, 5 AMP
FS
FREEZESTAT SWITCH (OPTIONAL ACCESSORY) OPEN @ 26˚ F
HP
HIGH PRESSURE SWITCH (OPTIONAL ACCESSORY) OPENS @ 280 PSIG
HTR 1
ELECTRIC HEATER (OPT. ACCSSRY: ALL KW ELEC HEAT)
HTR 2
ELECTRIC HEATER (OPT. ACCSSRY: 7.5, 10, 15, 20 & 25 KW ELEC HEAT)
HTR 3
ELECTRIC HEATER (OPT. ACCSSRY: 20 & 25 KW ELEC HEAT)
HTR 4
ELECTRIC HEATER (OPT. ACCSSRY: 15, 20 & 25 KW ELEC HEAT)
HTR 5
ELECTRIC HEATER (OPT. ACCSSRY: 20 & 25 KW ELEC HEAT)
HTR 6
ELECTRIC HEATER (OPT. ACCSSRY: 20 & 25 KW ELEC HEAT)
K1
RELAY INDOOR FAN MOTOR
RELAY ELECTRIC HEATER
K2
K3
RELAY ELECTRIC HEATER, 24 VDC COIL
K7
RELAY LIMIT TRIP, 25 VDC COIL
LP
LOW PRESSURE SWITCH (OPTIONAL ACCESSORY) OPEN @ 7 PSIG
LS
LIMIT SWITCH, ELECTRIC HEAT (PART OF ELEC HEAT ACCESSORY)
M1
CONTACTOR, COMPRESSOR & OUTDOOR FAN
M2
CONTACTOR, ELECTRIC HEAT, 230V COIL
M3
CONTACTOR, ELECTRIC HEAT, 230V COIL
PTCR
START ASSIST (OPTIONAL DEVICE)
RC1/RC2
COMPRESSOR START & OUTDOOR FAN RUN CAPACITOR
RC1
COMPRESSOR START CAPACITOR (ALTERNATE)
RC2
OUTDOOR FAN RUN CAPACITOR (ALTERNATE)
RC3
INDOOR FAN RUN CAPACITOR
RVS
REVERSING VALVE SOLENOID
S2/P2
SOCKET/PLUG CONNECTION ON FAN CONTROL BOARD, LOW VOLTAGE
S3/P3
SOCKET/PLUG CONNECTION ON FAN CONTROL BOARD, LINE VOLTAGE
S4/P4
SOCKET/PLUG CONNECTION ON ID FAN MOTOR, 24V
S3/P3
SOCKET/PLUG CONNECTION ON ID FAN MOTOR, 230V
T1
TRANSFORMER, 24V, 40 VA
TB2
TERMINAL BLOCK ECM MOTOR "SPEED" CONNECTIONS
IDENTIFIED TERMINAL ON RUN CAPACITOR
ROOM THERMOSTAT 24V CONNECTIONS
TB1 ON FAN/ELEC HEAT CONTROL BOARD
FACTORY WIRING AND DEVICES
OPTIONAL WIRING AND DEVICES
FIELD WIRING
27

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Thru 060B1hh024B1hh030B1hh036B1hh042B1hh048 ... Show all