Drive Selection - York Sun Select YV28 Manual

Table of Contents

Advertisement

Table 58: Belt tension
Size
Motor-Static
Deflection
force (lb)
7.5HP - STD
YV28
10HP - MED
15HP - HIGH
7.5HP - STD
YV30
10HP - MED
15HP - HIGH
7.5HP - STD
YV35
10HP - MED
15HP - HIGH
10HP - STD
YV40
15HP - MED
20HP - HIGH
10HP - STD
YV50
15HP - MED
20HP - HIGH

Drive selection

1.
Determine the required airflow.
2.
Calculate or measure the amount of external
static pressure.
3.
With the operating point determined from
the previous steps, locate this point on the
appropriate supply air blower performance
table. Linear interpolation may be necessary.
4.
Note the RPM and BHP from the previous
step and locate the appropriate motor and/or
drive.
Table 59: Example supply air blower performance
Air flow
0.3
0.4
(CFM)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard 7.5HP and field drive
8000
573
2.29
599
2.53
649
9000
606
2.92
631
3.15
678
10000
642
3.62
665
3.85
711
11000
680
4.41
702
4.64
745
12000
721
5.31
741
5.55
782
13000
763
6.36
783
6.60
822
Note: Blower performance includes gas heat exchangers and 2-in. filters. See the Static resistance
table for additional applications. See the RPM selection table to determine the required motor sheave
setting and to determine the maximum continuous BHP. kW = BHP x 0.93
Table 60: Example RPM selection
Model
HP
Max BHP
7.5
8.24
YV28
10
10.90
15
16.13
Belt tension
Max PRM
Deflection
distance (in.)
5.78
0.4
4.48
0.4
1100
5.72
0.4
5.9
0.4
6.91
0.4
1100
5.93
0.4
5.78
0.4
4.48
0.4
1150
5.72
0.4
7.42
0.4
8.85
0.4
1150
7.23
0.4
7.42
0.4
8.85
0.4
1150
7.23
0.4
Available external static pressure - IWG
0.6
0.8
1
Standard 7.5HP and drive
2.98
696
3.39
742
3.78
786
3.59
724
4.01
768
4.41
810
4.29
754
4.72
796
5.15
837
5.09
787
5.54
827
6.00
867
6.02
822
6.50
861
6.99
899
7.10
860
7.61
897
8.14
933
Motor
Blower
6 turns open 5 turns open 4 turns open 3 turns open 2 turns open
sheave
sheave
1VP65 - 1 3/8
1B5V124
2VP60- 1 3/8
2B5V94
2VP60- 1 5/8
2B5V86
Johnson Controls Ducted Systems
5.
Review the BHP compared to the motor
options available. Select the appropriate
motor and/or drive.
6.
Review the RPM range for the motor options
available. Select the appropriate drive if
multiple drives are available for the chosen
motor.
7.
Determine the turns open to obtain the
required operation point.
Example
1.
9000 CFM
2.
1.2 IWG
3.
Using the supply air blower performance table
below, the following data point was located:
810 RPM and 4.82 BHP.
4.
Using the following RPM selection table, Size X
and Model Y is found.
5.
4.82 BHP does not exceed the maximum
continuous BHP rating of any of the three
motor options, so all three motors are still
eligible for selection.
6.
810 RPM falls within the range of the 7.5-HP
drive.
7.
Using the 7.5-HP motor, 2.5 turns open
achieves 810 RPM.
1.2
1.4
1.6
Medium 10HP and drive
4.16
828
4.55
869
4.95
910
4.82
851
5.24
892
5.67
931
5.58
877
6.04
916
6.51
955
6.47
906
6.96
943
7.47
981
7.49
936
8.02
973
8.58 1009 9.18 1045 9.81 1080 10.49 1115 11.21 1132 11.58
8.69
969
9.26 1005 9.88 1040 10.52 1075 11.22 1109 11.95 1143 12.74
717
745
772
848
884
920
945
985
1026
Installation Manual: YORK
1.8
2
2.2
High 20 HP and drive
5.36
949
5.79
988
6.25 1026 6.75 1045 7.00
6.13
970
6.60 1007 7.12 1045 7.66 1063 7.95
7.00
992
7.53 1029 8.09 1066 8.69 1084 9.01
8.01 1017 8.59 1054 9.21 1089 9.87 1107 10.21
1 turn open
800
827
855
956
992
1028
1066
1106
1147
Sun™ Select YV28 to YV50
®
2.4
2.5
-
-
Fully closed
882
1064
n/a
79