Vfd Customer Supplied Standard Static - York Sun Select YV28 Manual

Table of Contents

Advertisement

VFD Customer supplied standard static

Note:
MCA = minimum circuit ampacity
f/b = fuse/breaker
Table 36: YV28 to YV50 VFD Customer supplied standard static without power exhaust
Comp. 1
Comp. 2
Nominal
Size
unit
(tons)
voltage
RLA LRA RLA LRA RLA LRA
208-3-60
41.0
304
22.4
149
230-3-60
41.0
304
22.4
149
YV28
(27.5)
460-3-60
19.2
147
10.6
75
575-3-60
16.7
122
7.7
54
208-3-60
44.2
315
25
164
YV30
230-3-60
44.2
315
25
164
(30)
460-3-60
22.4
158
12.8
100
575-3-60
18.6
136
9.6
78
208-3-60
48.1
351
27.6
191
230-3-60
48.1
351
27.6
191
YV35
(35)
460-3-60
24.7
197
12.8
100
575-3-60
22.4
135
9.6
78
208-3-60
48.1
351
27.6
191
230-3-60
48.1
351
27.6
191
YV40
(40)
460-3-60
24.7
197
12.8
100
575-3-60
22.4
135
9.6
78
208-3-60
67.3
485
39.1
267
YV50
230-3-60
67.3
485
39.1
267
(50)
460-3-60
32.7
215
18.6
142
575-3-60
26.3
175
15.4
103
Table 37: YV28 to YV50 VFD Customer supplied standard static with on/off power exhaust
Comp. 1
Comp. 2
Nominal
Size
unit
(tons)
voltage
RLA LRA RLA LRA RLA LRA
208-3-60
41.0
304
22.4
149
230-3-60
41.0
304
22.4
149
YV28
(27.5)
460-3-60
19.2
147
10.6
75
575-3-60
16.7
122
7.7
54
208-3-60
44.2
315
25
164
230-3-60
44.2
315
25
164
YV30
(30)
460-3-60
22.4
158
12.8
100
575-3-60
18.6
136
9.6
78
208-3-60
48.1
351
27.6
191
230-3-60
48.1
351
27.6
191
YV35
(35)
460-3-60
24.7
197
12.8
100
575-3-60
22.4
135
9.6
78
208-3-60
48.1
351
27.6
191
230-3-60
48.1
351
27.6
191
YV40
(40)
460-3-60
24.7
197
12.8
100
575-3-60
22.4
135
9.6
78
208-3-60
67.3
485
39.1
267
230-3-60
67.3
485
39.1
267
YV50
(50)
460-3-60
32.7
215
18.6
142
575-3-60
26.3
175
15.4
103
56
Installation Manual: YORK
Comp. 3
OD fan
OD fan
Supply
Supply
motors
motors
blower
blower
each
each
motor
FLA
LRA
FLA
22.4
149
4.0
21.0
19.4
22.4
149
4.2
21.0
19.4
10.6
75
2.1
10.5
9.7
7.7
54
1.6
7.8
8.0
25
164
4.0
21.0
19.4
25
164
4.2
21.0
19.4
12.8
100
2.1
10.5
9.7
9.6
78
1.6
7.8
8.0
27.6
191
4
21.0
19.4
27.6
191
4.2
21.0
19.4
12.8
100
2.1
10.5
9.7
9.6
78
1.6
7.8
8.0
27.6
191
4
21.0
25.0
27.6
191
4.2
21.0
25.0
12.8
100
2.1
10.5
12.5
9.6
78
1.6
7.8
10.0
39.1
267
7.2
39.6
25.0
39.1
267
6.8
39.6
25.0
18.6
142
3.4
19.8
12.5
15.4
103
2.7
15.8
10.0
Comp. 3
OD fan
Supply
120V
motors
blower
trans
each
motor
FLA
FLA
FLA
22.4
149
4.0
21.0
19.4
22.4
149
4.2
21.0
19.4
10.6
75
2.1
10.5
9.7
7.7
54
1.6
7.8
8.0
25
164
4.0
21.0
19.4
25
164
4.2
21.0
19.4
12.8
100
2.1
10.5
9.7
9.6
78
1.6
7.8
8.0
27.6
191
4
21.0
19.4
27.6
191
4.2
21.0
19.4
12.8
100
2.1
10.5
9.7
9.6
78
1.6
7.8
8.0
27.6
191
4
21.0
25.0
27.6
191
4.2
21.0
25.0
12.8
100
2.1
10.5
12.5
9.6
78
1.6
7.8
10.0
39.1
267
7.2
39.6
25.0
39.1
267
6.8
39.6
25.0
18.6
142
3.4
19.8
12.5
15.4
103
2.7
15.8
10.0
Sun™ Select YV28 to YV50
®
Johnson Controls Ducted Systems
Fuse is a dual element, time delay type
Breaker is a HACR type per NEC
Min
Max
disconnect
120 V
f/b
rating
MCA
trans
A
motor
size
FLA
LRA
A
FLA
144.4
14.4
131
150
139
144.4
13.0
132
150
140
72.2
6.5
63
80
67
59.1
5.2
51
60
53
144.4
14.4
140.7
175
149
144.4
13.0
141.5
175
150
72.2
6.5
72
90
76
59.1
5.2
57
75
60
144.4
14.4
151
175
160
144.4
13.0
152
175
160
72.2
6.5
75
90
79
59.1
5.2
62
80
64
173.44
14.4
156
200
166
173.44
13.0
157
200
167
86.72
6.5
77
100
82
71.77
5.2
64
80
67
173.44
14.4
216
275
229
1351
173.44
13.0
215
275
227
1351
86.72
6.5
104
125
110
71.77
5.2
84
110
90
Electric heat option
field installed kit
MCA
A
Model
kW Stages
A
144.4
4.0
21.0
14.4
139
144.4
4.2
21.0
13.0
141
72.2
2.1
10.5
6.5
68
59.1
1.6
7.8
5.2
54
144.4
4.0
21.0
14.4
149
144.4
4.2
21.0
13.0
150
72.2
2.1
10.5
6.5
76
59.1
1.6
7.8
5.2
60
144.4
4
21.0
14.4
159
144.4
4.2
21.0
13.0
160
72.2
2.1
10.5
6.5
79
59.1
1.6
7.8
5.2
65
173.44
7.2
39.6
14.4
171
173.44
6.8
39.6
13.0
171
86.72
3.4
19.8
6.5
84
71.77
2.7
15.8
5.2
69
173.44
7.2
39.6
14.4
231
173.44
6.8
39.6
13.0
228
86.72
3.4
19.8
6.5
111
71.77
2.7
15.8
5.2
90
Max
Min
MCA
f/b
disconnect
with
size
rating/120V
120 V
with
trans
trans
120V
A
trans
LRA
FLA
LRA
A
830
146
175
155.9
844.8
830
145
175
155.3
843.4
411
70
80
74.8
417.7
320
56
70
59.5
325.5
871
155
175
165.6
885.8
871
154
175
164.9
884.4
472
78
100
83.5
478.7
382
62
80
66.0
387.5
961
165
200
176.1
975.8
961
165
200
175.4
974.4
511
81
100
86.1
517.7
381
67
80
70.4
386.5
990
171
200
182.5 1004.8
990
170
200
181.8 1003.4
526
84
100
89.4
532.2
394
69
90
72.7
399.2
231
275
245.8 1365.2
228
275
242.3 1363.8
665
111
125
117.9
671.4
516
90
110
95.6
521.2
Max
Min
MCA
f/b
disconnect
Max
disconnect
with
size
rating/120V
f/b
rating
120V
with
size
trans
120V
A
A
trans
FLA
LRA
FLA
A
175
149
872
154
175
165
175
150
872
154
175
165
80
72
432
74
90
80
70
57
336
59
75
63
175
158
913
163
200
175
175
160
913
163
200
175
90
81
493
82
100
88
75
64
398
65
80
70
200
169
1003
173
200
185
200
170
1003
173
200
185
100
83
532
85
100
91
80
68
397
70
90
74
200
183
1070
185
225
199
200
183
1070
184
225
197
100
90
565
91
110
97
90
73
426
74
90
79
275
246
1430
245
300
262
275
243
1430
241
300
258
125
118
705
117
150
126
110
96
548
95
110
102
Min
trans
LRA
887
885
439
341
928
926
500
403
1018
1016
539
402
1084
1083
572
431
1444
1443
711
553