COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
INDOOR COIL MODEL NO.
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
Air Handler
Coil
N1AHB1293
G2FD030S17
N1AHB1293
G2FD036S17
F2RP036N93
Unitary Products Group
H1RA030S78A
G2FD030S17
IDCFM
650
ID DB (°F)
85
80
ID WB (°F)
72
67
T.C.
26.4
25.3
S.C.
15.4
15.6
K.W
2.39
2.35
T.C.
25.4
23.9
S.C.
15.3
15.1
K.W
2.67
2.62
T.C.
24.4
22.5
S.C.
15.3
14.6
K.W
2.71
2.64
T.C.
22.5
20.1
S.C.
14.7
13.8
K.W
2.98
2.89
T.C.
20.6
17.7
S.C.
14.2
13.0
K.W
3.00
2.88
T.C.
17.8
15.2
S.C.
13.3
12.4
K.W
3.13
3.02
T.C.
S.C.
KW
1.00
1.00
1.00
1.02
1.03
1.03
1.02
1.03
1.03
850
70
85
80
57
72
67
24.0
26.6
25.7
15.4
16.2
16.7
2.32
2.53
2.49
21.8
25.7
24.6
14.4
16.4
16.6
1.40
2.82
2.76
19.6
24.9
23.4
13.4
16.6
16.6
2.55
2.86
2.80
17.6
23.2
21.1
12.7
16.4
15.9
2.80
3.14
3.05
15.6
21.5
18.8
11.9
16.3
15.2
2.80
3.17
3.05
13.3
18.7
15.9
11.4
15.4
14.3
2.93
3.30
3.18
036-21103-003 Rev. A (0403)
1050
70
85
80
57
72
67
24.6
26.7
26.1
16.8
16.9
17.8
2.46
2.56
2.53
22.8
26.1
25.2
16.2
17.4
18.2
2.71
2.93
2.88
20.9
25.4
24.3
15.7
17.9
18.5
2.71
2.91
2.85
18.6
23.9
22.1
14.7
18.1
17.9
2.95
3.27
3.18
16.3
22.4
19.8
13.8
18.3
17.3
2.95
3.24
3.12
14.0
19.5
16.7
13.1
17.4
16.1
3.08
3.37
3.23
70
57
25.2
18.2
2.50
23.7
18.1
2.83
22.2
17.9
2.77
19.6
16.8
3.08
16.9
15.6
3.00
14.7
14.7
3.13