PHYSICAL AND ELECTRICAL DATA - 1 & 3 Phase
MODEL
Unit Supply Voltage
1
Normal Voltage Range
Minimum Circuit Ampacity
Max. Qvercurrent Device Amps
Compressor Type
Rated Load
Compressor Amps
Locked Rotor
Crankcase Heater
Fan Motor Amps
Rated Load
Fan Diameter Inches
Rated HP
Fan Motor
Nominal RPM
Nominal CFM
Face Area Sq. Ft.
Coil
Rows Deep
Fin / Inches
Liquid Line OD
Vapor Line OD
3
Unit Charge (Lbs. - Oz.)
Charge Per Foot, Oz.
Operating Weight Lbs.
1. Rated in accordance with ARI Standard 110, utilization range "A".
2. Dual element fuses or HACR circuit breaker.
3. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than
15 feet, refer to publication 035-15893-60*
2
H1RA018S78 H1RA024S78 H1RA030S78 H1RA036S78 H1RA036S50 H1RA048S50 H1RA060S50
230 – 1 – 50
207 to 253
9.8
14.6
2
15
25
Recip
Recip
7.4
11.3
53
65
No
No
.5
.5
18
18
1/12
1/12
970
970
1,650
1,650
8.00
8.00
1
1
14
14
3/8
3/8
3/4
3/4
3 - 13
3 - 14
0.66
0.66
118
123
20.4
20.8
35
35
Recip
Recip
15.2
15.5
90
82
No
No
1.8
1.8
18
18
1/4
1/4
900
900
2,350
2,350
9.15
9.15
1
1
16
16
3/8
3/8
3/4
3/4
3 - 15
4 - 11
0.68
0.68
135
137
All dimensions are in inches. They are subject to
change without notice. Certified dimensions will be
provided upon request.
DIMENSIONS
UNIT
MODEL
H1RA
1
A
018S78
17
024S78
17
030S78
19
036S78
19
036S50
19
048S50
27
060S50
39
1. Including fan guard
380/415 – 3 – 50
342 to 455
7.3
10.8
15
15
Recip
Recip
5.2
7.2
39
53
No
No
.8
1.8
18
22
1/4
1/3
1,100
1,075
2,250
3,200
9.15
15.72
1
1
18
18
3/8
3/8
3/4
7/8
4 - 11
7 - 10
0.68
0.70
137
206
REFRIGERANT
CONNECTION
(INCHES)
LINE SIZE
B
C
Liquid
Vapor
35
23
35
23
35
23
3/4"
35
23
3/8"
35
23
37
27
7/8"
37
27
Unitary Products Group
13.3
20
Recip
9.2
79
No
1.8
22
1/3
1,075
3,300
23.58
1
18
3/8
7/8
9 - 12
0.70
228