COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
INDOOR COIL MODEL NO.
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
Air Handler
Coil
NAHD2093
G2FD060S24
F2RP060N93
Unitary Products Group
H1RA060S50A
G*FD060S24A
IDCFM
1650
ID DB (°F)
85
80
ID WB (°F)
72
67
T.C.
65.0
62.4
S.C.
41.8
41.5
K.W
5.40
5.36
T.C.
63.9
60.7
S.C.
41.8
41.1
K.W
6.11
6.04
T.C.
62.8
59.1
S.C.
41.8
40.7
K.W
6.21
6.12
T.C.
60.6
55.3
S.C.
40.9
39.4
K.W
6.92
6.74
T.C.
58.5
51.5
S.C.
40.1
38.2
K.W
7.03
6.76
T.C.
52.9
47.7
S.C.
38.7
36.7
K.W
7.31
7.09
T.C.
S.C.
KW
1.00
1.00
1.00
1.00
1.00
1.00
1900
70
85
80
57
72
67
59.6
65.8
62.8
41.0
44.7
44.0
5.28
5.81
5.76
56.5
64.7
61.4
39.8
44.7
43.7
5.91
6.57
6.49
53.5
63.5
60.0
38.6
44.6
43.5
5.94
6.63
6.53
49.3
61.5
56.6
36.8
44.0
42.4
6.57
7.38
7.22
45.1
59.6
53.3
35.0
43.4
41.3
6.59
7.44
7.22
40.4
54.2
48.5
32.8
42.0
39.4
6.84
7.78
7.53
036-21103-003 Rev. A (0403)
2150
70
85
80
57
72
67
60.0
66.6
63.3
43.6
47.5
46.5
5.69
5.62
5.56
57.5
65.4
62.1
42.5
47.5
46.4
6.38
4.41
4.34
55.0
64.3
60.8
41.5
47.5
46.2
6.39
6.45
6.33
50.7
62.4
58.0
39.8
47.1
45.3
7.05
7.24
7.10
46.5
60.6
55.1
38.2
46.8
44.4
7.02
7.25
7.08
41.9
55.5
49.4
35.8
45.4
42.1
7.29
7.64
7.36
70
57
60.5
46.1
5.50
58.5
45.3
4.27
56.5
44.4
6.23
52.2
42.9
6.93
47.9
41.4
6.84
43.5
38.9
7.13
13