Application planning

4.1

Hardware configuration

Maximum configuration
● The integrated power supply of the interface module feeds 14 W into the backplane bus.
● A maximum of one power supply module (PS) upstream from the interface module and
● If you use a power supply module (PS) upstream from the interface module, the
Rules: Arrangement of the modules
The following table shows the slot number assignment:
Table 4- 1
Slot
0
1
2 - 31
See also
Setting up power segments (Page 36)
ET 200MP Distributed I/O System
System Manual, 01/2013, A5E03723484-01
Up to 12 I/O modules can be supplied this way. The exact number of operable modules is
the result of the power budget (see chapter Power budget calculation (Page 32)).
two downstream from the interface module is possible.
maximum possible configuration is a total of 32 modules (up to 30 modules downstream
from the interface module).
Figure 4-1
Maximum ET 200MP configuration
Assignment of slot numbers
Modules
Power supply module (optional)
Interface module
I/O modules /
max. 2 power supply modules, depending
on the configuration