Ip Router As A Coupler To The Ip Network - Siemens Synco 700 Series Basic Documentation

Communication via the knx bus
Hide thumbs Also See for Synco 700 Series:
Table of Contents

Advertisement

10BaseT interface
Rules
Allocation of IP
addresses
Note
Building Technologies
HVAC Products
8.1.2

IP router as a coupler to the IP network

The router can be connected via to the IP network via Ethernet cable and the
integral RJ45 socket of the IP router.
Cat5 cable
IP Ac
10BaseT
192.168.10.1
1.0.0
255.255.255.0
N146
Main line 1
Lc
1.1.0
N140/13
1.1.1
1.1.2
1.1.x
The IP router has a 10BaseT interface (Ethernet at 10 Mbit/s via Cat5 cable).
When using IP routers, the following rules must be observed:
• With an IP router used as an area coupler (IP Ac) no other IP routers may be
installed below the IP Ac in the topology.
• With an IP router used as a line coupler (IP Lc) no other IP routers may be
installed above the IP Lc in the topology.
When IP routers are used for coupling to an IP network, the following points must
be discussed with the IP network administrator:
• Automatic address assignment via DHCP (see section 8.3)
or
• Manual IP address assignment (see section 8.3)
and also:
IP routing, multicast addresses
IP subnet mask
IP standard gateway
This document does not deal with the technical aspects of Ethernet
communications.
Basic documentation: Communication via the KNX bus
Large plants
IP Network (Area line 0)
Lc
1.2.0
N140/13
1.2.1
1.2.2
1.2.x
81/120
CE1P3127en
30.08.2007

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents