Service tool OCI700.1
Installing the software
OCI700 service interface
Building Technologies
HVAC Products
5

Device addresses via ACS

5.1
Service tool OCI700.1 and ACS7... software
5.1.1

Overview

The OCI700.1 service tool is used for commissioning and diagnostics for devices in
the Synco, SIGMAGYR and ALBATROS ranges, and for the operation of plant via
the KNX bus or Local Process Bus (LPB) (see data sheet N5655).
When ordering, please use type code OCI700.1. No license is required for
operation. The tool is supplied as a complete kit in a service case:
• CD-ROM with
Operating software
Service software
Documentation
• OCI700 service interface
• USB cable, Type B socket
• KNX service cable, RJ45 For Synco devices
• LPB service cable, RJ12 For SIGMAGYR and ALBATROS controllers
The OCI700.1 service tool/ACS7... software are installed on a PC/laptop from the
CD-ROM. See data sheets N5640 and N5641 for details of the ACS7... software.
The OCI700 service interface converts the signals between the USB port on the
PC/laptop and the tool interface on the bus device (RJ45 connection).
There is no need to set parameters for the service interface. Only the central unit
(OCI700-KNX, see section 5.1.2) needs to be selected via the software, after which
communication is established with the device (and other devices on the bus).
KNX service cable
RJ45
connector
Bus
conduit box
RM..
Basic documentation: Communication via the KNX bus
Device addresses via ACS
(not illustrated below)
USB
Service
interface