Device Address For Rmz792 Bus Operator Unit - Siemens Synco 700 Series Basic Documentation

Communication via the knx bus
Hide thumbs Also See for Synco 700 Series:
Table of Contents

Advertisement

Introduction
Note
Bus power supply
Modifying the device
address
Note
Operating page
Setting the device address
Building Technologies
HVAC Products
5.8

Device address for RMZ792 bus operator unit

The RMZ792 bus operator unit is used for remote operation of up to 150 Synco
700 bus devices including OZW77x central communication units and RXB/RXL
room controllers in a KNX network. Access to the bus devices is via the device list.
There is no access to Synco 900 type QAX910 central apartment units, area/line
couplers, IP routers or third-party devices.
The RMZ792 bus operator unit cannot be used to commission the Synco devices.
This is in contrast to the RMZ790 and RMZ791 operator units which can be used
for local commissioning of the Synco devices, but not for remote operation of other
Synco devices via the bus.
For more information on the RMZ792 bus operator unit, refer to data sheet N3113
and the basic documentation, P3113.
The RMZ792 bus operator unit does not power the bus.
Decentral or central bus power supply is required for communication via the KNX
bus (see section 2.2).
The bus operator unit is connected to an external AC 24 V power supply
(recommended for fixed operator units, e.g. installed in control panel doors).
The factory-setting is device address 255. For communication via KNX, this device
address must be modified.
If there are no couplers or IP routers, the factory-set area/line address 0.2 is used.
The individual device address can now be set.
• Via the "Communication" operating page
(either set device address or search automatically for a device address)
• Via ACS Service and manual address assignment
The RMZ792 bus operator unit cannot be used to set the area, line and device
addresses of other bus devices.
Access to the "Communication" page is at the Password level
following path:
Main menu > Commissioning > Communication
Communication
Area:
Line:
Device address:
Search address:
Select the "Device address" line by rotating the knob, then press the knob to enter
the required device address. Press the knob to confirm the setting.
Basic documentation: Communication via the KNX bus
Device addresses via ACS
0
2
255
---
and via the
53/120
CE1P3127en
30.08.2007

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents