Setting A Time Slave Remotely - Siemens Synco 700 Series Basic Documentation

Communication via the knx bus
Hide thumbs Also See for Synco 700 Series:
Table of Contents

Advertisement

Settings
Example
Sends
time of day:
10:15
Clock time operation:
Master
Modifying the
time and date
Note
Clock time operation:
Slave with
"Rem set clock slave:" Yes
62/120
Building Technologies
HVAC Products
Clock time op.: Auto
Clock time op.: Slave
Clock time op.: Master
Receives:
10:15
Clock time operation:
Clock time operation:
Slave
Slave
The time and date in the time master can be modified as follows:
• By the user, on the time master
• By the user, by remote adjustment of the time slave
A user-adjustment of the time or date can be synchronized by pressing the rotary
knob.
Only one bus device at a time can be the time master in a network. In relation to
the date and time, the other bus devices must be set as time "slaves" or set to
"Autonom."
6.1.3

Setting a time slave remotely

The operating line "Rem set clock slave" can be used to configure a time slave so
that the time and date can be set by an operator. The new values are then
transmitted via the KNX bus to the time master.
Main menu > Commissioning > Communication > Basic settings
Basic settings
Device address:
Dec bus power supp:
Clock time op:
Rem set clock save:
Remote time-slave setting for RM... controller
Default.
Yes
Settings
No/Yes
Basic documentation: Communication via the KNX bus
Basic communication settings
The RM... controller does not receive or transmit the time
or date (The device has its own time and date).
The RM... controller receives the time and date from the
time master.
The RM... controller transmits the time and date in a 10
minute cycle over the KNX bus, starting from the last
time-synchronization
Receives:
Has its own
10:15
time of day
Clock time operation:
Autonomous
1
On
Slave
Yes
Receives:
10:15
Time of day for
timer function
CE1P3127en
30.08.2007

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents