4 Monitoring the Temperature in Control Panel with the Main Unit and the Software Tool
4-2
Functions of Monitoring the Tem-
perature in the Control Panel
This section describes each function related to monitoring of temperature inside the control panel.
4-2-1
Functions of Monitoring the Temperature in Control Panel with
the Main Unit and the Software Tool
This section describes each function of monitoring the temperature in the control panel with the Main
Unit and the software tool.
K6PM-TH Sensor Position Registration, and K6PM-TH Sensor Angle
Deviation Notification
If the infrared thermal sensor drops or gets tilted, it will not be possible to perform correct temperature
monitoring.
Therefore, it is possible to register the correct position of each connected infrared thermal sensor in the
Main Unit, and if a deviation of the installation angle of the K6PM-TH sensor occurs, the user can be
notified about the same.
In the factory default settings, this function of the infrared thermal sensors is disabled. To enable this
function, change the DIP switch Pin 7 on the side surface of the infrared thermal sensor to ON (with
detection).
Note Since the K6PM-TH sensor angle deviation notification function detects the change in the angle in the
direction of gravity, the change cannot be detected for movement in the horizontal direction and rotation
performed with the direction of gravity as an axis.
 How to Register the K6PM-TH Sensor Location
Register the sensor position by either one of the following methods:
• On the Setting sensor Screen of the software tool, click the Position registration Button for
each sensor.
• Register the sensor position by communications.
• Long-press the K6PM-TH sensor angle deviation reset switch on the side of the sensor for at least
3 seconds.
 K6PM-TH Sensor Angle Deviation Notification Method
The K6PM-TH sensor angle deviation can be checked by any of the following methods:
• Display the angle deviation for each sensor on the Setting K6PM Screen of the software tool.
• Display the angle deviation for each sensor on the Monitoring K6PM Screen of the software tool.
• Display the angle deviation as a Main Unit error and K6PM-TH sensor error for each Main Unit on
the Device List of K6PM Screen of the software tool.
• The bit indicating the K6PM-TH sensor angle deviation error for the sensor status turns ON. It can
be read through communications.
• The product status (MS) LED on the Main Unit blinks red.
• The alarm or other indicator on the sensor blinks.
K6PM-TH Thermal Condition Monitoring Device User's Manual (H231)