Fan Modules

The fan module can be configured as either draw-thru or blow-thru. Review the submittals and unit
tagging information prior to assembly to determine placement.

Fan Isolation

The fan-and-motor assembly is internally isolated. The fan and motor bases are bolted to a
minimum of four spring isolators. The isolators are secured to the fan module support base.
Shipping tie-down bolts are bolted adjacent to the isolators between the fan isolation base and the
isolator support frame. The shipping tie-downs secure the isolation base to the support assembly
to prevent any damage to the fan module during shipment.
Note: Remove the tie-downs only if the factory-provided isolation is to be used.

Removing Shipping Tie-Downs

There are three types of shipping tie-downs used to secure the isolation base, depending on unit
size:
Figure 32. Isolator tie-down removal for
unit sizes 3 to 57
Bolt, isolator
tie-down
CLCH-SVX03C-EN
Sizes 3 to 8 use a 3/8 x 1-inch pipe (see
Sizes 10 to 57, use a tie-down bolt and shim (see
Sizes 66 to 120 and plenum fans use a tie-down angle and bolt (see
Figure 33. Isolator tie-down removal for unit sizes 66 to 120 and plenum
Component Installation Requirements
Figure
32).
Figure
fans
Screw (4 per angle)
Lockwasher and hex nut
Angle, isolator
tie-down (4 required)
32).
Figure
33).
39