Activation - GEM 4242 Operating Instructions Manual

Devicenet, combi switchbox with integrated pilot valve
Table of Contents

Advertisement

Class
Inst.
Attr.
Fh
17h
1h
Programing error
Fh
18h
1h
Pneumatic error
Fh
19h
1h
Internal error
Fh
1Ah
1h
Stroke reduction warning
Fh
1Bh
1h
Valve cycles user
Fh
1Ch
1h
Valve cycles total

14 Activation

Activate the combi switchbox after end position programming by a 24 V DC signal to pin 6.
www.gemu-group.com
Parameter
Lengt
h
1 byte USINT
1 byte USINT
1 byte USINT
1 byte USINT
4 byte UDINT
4 byte UDINT
29 / 36
Data
Ac-
Stand-
type
cess
ard
value
Get
1
0 = Programming OK
1 = not calibrated
2 = no stroke
3 = stroke < min. stroke
4 = Sensor error position closed
5 = Sensor error position open
6 = Sensor error position closed
+ open
Get
0
0 = Pneumatic OK
1 = Pneumatic error position
closed
2 = Pneumatic error position
open
3 = Pneumatic error middle
position
Get
0
0 = Device OK
1 = un-valid crc-check
2 = un-valid serial number
3 = Memory error
Get
0
0 = Stroke OK
1 = Stroke reduction position
closed
2 = Stroke reduction position
open
3 = Stroke reduction position
closed + open
Get/Set 0
Resettable to 0,
display of numerical values 0 -
 429496729
Get
0
Display of numerical values 0 -
 429496729
14 Activation
Value range
GEMÜ 4242
DeviceNet

Hide quick links:

Advertisement

Table of Contents
loading