13 Specific data - DeviceNet

13 Specific data - DeviceNet

13.1 General data

Communication modes:
Class
Inst.
1h
1h
1) Use EDS file in accordance with revision status of the device
Note: Download EDS files from www.gemu-group.com
13.2 Net topology - DeviceNet system
To avoid malfunction the trunk cable is fitted with resistors on both sides. The drop cables do not require bus ends.
V+
V-
CAN_H
120 Ω
1/4 W
CAN_L
Shield
Protective
Protective
earth
earth
Drop cable
Baud rate [kBaud]
125
500 m
250
250 m
500
100 m
GEMÜ 4242
DeviceNet
Function, Polling, Change of state, Cyclic, Bit strobe
Attr.
Function
1h
Vendor ID
2h
Product Type
3h
Product Code
4h
Rev.
5h
Status
6h
Series No.
7h
Name
120 Ω
1/4 W
Trunk cable
Maximum cable length
Trunk cable
Thick cable
100 m
100 m
100 m
Identity
869
48
4242
1)
2.2
Device status according to DeviceNet specifications
Continuous serial number
4242 DN combi switchbox
Thin cable
Max. cable length per
drop cable
6 m
6 m
6 m
26 / 36
Value
Drop cable
Max. drop cable accu-
mulated length
156 m
78 m
39 m