GEM 4242 Operating Instructions Manual page 10

Devicenet, combi switchbox with integrated pilot valve
Table of Contents

Advertisement

4 Correct use
4.3 Product with special function X
The product with the special version X order option is intended for use in potentially explosive areas of zone 2 with gases,
mists or vapours and zone 22 with combustible dusts in accordance with EU directive 2014/34/EU (ATEX).
The product has the following explosion protection marking:
Gas:
II 3G Ex ec nC IIC T4 Gc X
Dust:
II 3D Ex tc IIIC T 80 °C Dc X
Type examination certificate: IBExU18ATEXB008 X
The product has been developed in compliance with the following harmonised standards:
DIN EN 60079-0:2012+A11:2013
DIN EN 60079-7:2015
DIN EN 60079-15:2010
DIN EN 60079-31:2014
Use of the product is permissible in the following ambient temperature ranges: 0 to +60 °C
For use in potentially explosive areas, the following conditions or operation limits must be observed:
Index X is applied to the ATEX marking.
The following special conditions must be complied with:
1. Connection cables and connectors must be protected from damage.
2. Layers of dust > 5 mm must be removed.
3. Warning label "Danger from electrostatic build-up".
4. Warning label "Do not disconnect when live".
GEMÜ 4242
DeviceNet
10 / 36
www.gemu-group.com

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents