9 Assembly and installation
9.5 Combi switchbox mounting
M16 x 1 - WAF 24
M12 x 1 - WAF 20
The thread size depends
on the valve to which
the combi switchbox
is mounted.
1. Move the actuator to the open position.
2. Place the product as far as it will go into the actuator opening, insert adapter 3 (see chapter 9.3) or stroke limiter 1 (see
chapter 9.4) and screw in clockwise against the initial spring tension.
3. Use the spanner flat of the travel sensor to tighten the product.
4. Turn the housing clockwise to align the pneumatic or electrical connections.
5. Initialize the product.
Incorrect installation of the product.
▶ Damage to the housing.
Only tighten the product using the spanner flats provided for this purpose.
●
6. The product with mounting kit is fully assembled.
7. The product with mounting kit and adapter is fully assembled.
8. The product with mounting kit and stroke limiter is fully assembled.
GEMÜ 4242
DeviceNet
6
CAUTION
20 / 36
www.gemu-group.com