8.2.4

Replacing a fuse in the Adapter Module 600

Preparatory steps
● Disconnect the drive line-up from the power supply
● Allow unimpeded access to the Adapter Module 600 (AM600).
● Check that the device is in a no-voltage condition
The fuses to protect the conductors of the Hybrid Cable are integrated in the Adapter Module
600.
Danger to life due to electric shock when replacing a fuse
Because of the DC link capacitors, a hazardous voltage is present for up to five minutes
after the power supply has been switched off.
Contact with live parts can result in death or serious injury.
• Switch the power supply off before replacing the fuse.
• Wait at least 5 minutes after switching off.
• Before starting any work, also check that the system is in a voltage-free state by
• Only use the following replacement fuses:
SINAMICS S120M Distributed Drive Technology
Manual, (GH12), 12/2014, 6SL3097-4AW00-0BP3
DANGER
measuring at the DC link terminals DCP and DCN.
– SIBA
– Type URZ 14 x 51 mm, gR 800 VDC, 32 A
– Part No. 5012006
– Siemens article number: 6SL3566-7DA00-0AA0.
Service and maintenance
8.2 Replacing components
151