Parameter Assignment And Structure Of The Parameter Data Record For Pulse Width Modulation Operating Mode - Siemens SIMATIC ET 200SP Manual

Digital output module dq 4x24vdc/2a hs 6es7132-6bd20-0da0
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Parameter data records
A.3 Parameter assignment and structure of the parameter data record for pulse width modulation operating
mode
A.3
Parameter assignment and structure of the parameter data record
for pulse width modulation operating mode
Parameter assignment in the user program
You can reassign the parameters of the module in RUN. For example, you can change the
period of individual channels in "Pulse width modulation" operating mode in RUN without this
having an effect on the other channels.
Changing parameters in RUN
The "WRREC" instruction is used to transfer the parameters to the module using data record
128. The parameters set in STEP 7 are not changed in the CPU, which means the
parameters set in STEP 7 are valid again after a restart.
Note
Changing parameters in RUN
A parameter data record that has content different from the startup parameter assignment
can result in a brief exit from clocked mode and renewed synchronization with the fieldbus
cycle.
STATUS output parameter
The module ignores errors that occur during the transfer of parameters with the "WRREC"
instruction and continues operation with the previous parameter assignment. The STATUS
output parameter contains a corresponding error code.
The description of the "WRREC" instruction and the error codes is available in the STEP 7
online help.
110
Digital output module DQ 4x24VDC/2A HS (6ES7132-6BD20-0DA0)
Manual, 06/2018, A5E32855695-AC