Checking The Function Of The Safety Equipment; Checking The Electrical Connections; Filling, Flushing And Checking The Solar Thermal System For Leaks - Viessmann VITOSOL-F Service Instructions Manual

Table of Contents

Advertisement

Commissioning, inspection, maintenance
Checking pressure conditions, adjusting the...
The following values result at 10 m static head (example)
Solar thermal system pressure
1
Supplement, static head 0.1 bar/m
2
System pressure (pressure gauge)
3
Pressure reserve for venting
Charge pressure
System pressure (pressure gauge) af-
ter venting
Deduction for hydraulic seal
4
Supplement per m of height difference
between pressure gauge and expan-
sion vessel
5
Pre-charge pressure, expansion
vessel
Note
Record the "pre-charge pressure" on
the expansion vessel.

Checking the function of the safety equipment

Check the safety valve:
Response pressure
Correct installation, with discharge pipe

Checking the electrical connections

Check the tightness of the electrical plug-in connectors
and cable grommets
check cables for damage.
;

Filling, flushing and checking the solar thermal system for leaks

!
Please note
Filling and commissioning the solar thermal sys-
tem without first safeguarding the heat transfer
results in thermal stress.
Cover the collectors and keep them covered
until the heat transfer has been regulated.
8
(cont.)
Vitosol-FM
3.0 bar
1.0 bar
4.0 bar
+ 0.1 bar
4.1 bar
4.0 bar
0.3 bar
0.1 bar x 1 m = 0.1 bar
3.8 bar
Accessories for flushing and filling the solar thermal
system:
Flushing and filling facility (filling trolley and
charging station)
These contain a high speed pump with a high
pump rate, a filter and a container for heat transfer
medium.
Fill valve set, consisting of shut-off valve, drain
valve and fill valve.
Flush the solar thermal system with heat transfer
medium. Otherwise there is a risk that residual water
from flushing may become mixed with the heat trans-
fer medium. This would alter the properties of the
heat transfer medium.
Flush brazed copper pipes very thoroughly. Any
residual scale may compromise the operation of the
solar thermal system.
Vitosol-F
1.0 bar
1.0 bar
2.0 bar
+ 0.1 bar
2.1 bar
2.0 bar
0.3 bar
0.1 bar x 1 m = 0.1 bar
1.8 bar