Additional Fittings - Samson 46-5 Mounting And Operating Instructions

Differential pressure limiters with flow limitation, self-operated
Table of Contents

Advertisement

5.2 Additional fittings

Strainer
A strainer installed upstream in the flow pipe
holds back any dirt or other foreign particles
carried along by the medium. For example,
the SAMSON Type 1 NI Strainer is suitable
(u T 1010).
− Do not use the strainer to permanently
filter the process medium.
− Install the strainer upstream of the regu-
lator.
− The direction of flow must correspond to
the arrow on the valve body.
− The filter element must be installed to
hang downward.
− Allow sufficient space to remove the filter.
Shut-off valves
Install a hand-operated shut-off valve both
upstream of the strainer and at the outlet of
the return flow pipe (see Fig. 4). This allows
the plant to be shut down for cleaning and
maintenance, and when the plant is not used
for longer periods of time.
Pressure gauge
Install a pressure gauge at a suitable point to
monitor the pressures prevailing in the plant
(see Fig. 4).
Control line
Depending on the regulator version, a con-
trol line (standard: 6x1 mm pipe diameter)
must be adapted and mounted on site. Make
sure that the control line is free of dirt.
EB 3130 EN
min.
min.
3 x DN
3 x DN
Control
line
DN = Nominal size
Fig. 5: Control line connection, depending on
how the pipeline is routed
We recommend installing the control line for
tapping pressure from the pipeline at a dis-
tance of at least three times the nominal size
(DN) away from any pipe fittings (e.g. mani-
folds, bends, branches or other valves), that
may cause turbulence in the flow.
How the lines are routed generally de-
pends on the installation site. Preferably
connect the control line to the side of the
main pipe.
Î Do not change the pipe diameter of the
main pipeline with an eccentric reducer.
Î Refer to installation schematics (Fig. 4)
for line routing.
Mounting and start-up
DN
M
min.
3 x DN
21

Advertisement

Table of Contents
loading

This manual is also suitable for:

46-6

Table of Contents