Stationary installation
Do not mount on floor with
front side down
Battery Replacement
The UPS supports hot swapping. Battery replacement is possible
both when the power is turned OFF (while the power output is OFF)
and when the power is turned ON (while the power output is ON).
Precautions for Correct Use
• For battery replacement, hold down the "Buzzer Pause/Test"
switch on the unit for 10 seconds or longer to activate the battery
replacement mode. When "
completed.
* Activate the battery replacement mode while the "input power
supply" is turned ON.
If you replace the battery without activating the battery
replacement mode, the battery life may not be detected
accurately because the battery life counter is not reset.
• Do not replace the battery during backup operation. Otherwise, the
output stops.
The life of the battery used in the UPS is limited. This life changes
depending on the use environment and the frequency of backup
operation.
• As the battery life comes closer to its end, the battery deteriorates
more rapidly. Be careful.
The storage condition also affects the deterioration of the battery. As
the storage temperature becomes higher, the battery life becomes
shorter. Be careful.
Do not stack
To mount UPS on floor with its top side away
from you, ensure that its top side is not in
contact with wall.
" is displayed, the activation is
Battery check schedule and frequency
Ambient
6-Month Inspection 3-Month Inspection
temperature
Up to 1 year from the
55°C
date of purchase
Up to 1.5 years from
50°C
the date of purchase
Up to 3 year from the
40°C
date of purchase
Up to 6 year from the
25°C
date of purchase
Conformance to EC Directives
Applicable directives
• EMC Directives
• Low Voltage Directives
Principles regarding conformance
OMRON electronic devices that comply with EC Directives also
conform to the related EMC standards so that they can be more easily
built into other devices or the overall machine. The actual products
have been checked for conformity to EMC standards*.
Whether the products conform to the standards in the system used by
the customer, however, must be checked by the customer. EMC-
related performance of the OMRON devices that comply with EC
Directives will vary depending on the configuration, wiring, and other
conditions of the equipment or control panel on which the OMRON
devices are installed. The customer must, therefore, perform the final
check to confirm that devices and the overall machine conform to
EMC standards.
* Applicable EMC (Electromagnetic Compatibility) standards are as
follows: EMS (Electromagnetic Susceptibility): EN 61000-6-2, EMI
(Electromagnetic Interference): EN 61000-6-4, and EN 61000-6-4
Radiated emission: 10-m regulations
Low Voltage Directives
Always ensure that devices operating at voltages of AC 50 to 1,000 V
and DC 75 to 1,500 V meet the required safety standards. The
applicable directive is EN60950-1.
Conformance to EC Directives
This product complies with EC Directives. To ensure that the machine
or device in which the this product is used complies with EC
Directives, the product must be installed as follows:
• This product must be installed within a control panel.
• You must use reinforced insulation or double insulation for the
direct power supply equipment connected to this product.
• Models of this product that comply with EC Directives also conform
to the Common Emission Standard. Radiated emission
characteristics (10-m regulations), in particular, may vary
depending on the configuration of the control panel used, other
devices connected to the control panel, wiring, and other
conditions. Therefore, even when using a model of this product
that complies with EC Directives, you must confirm and ensure the
compliance to EC Directives of the entire machine or equipment.
• This is a Class A product (for industrial environments). In a
residential environment, it may cause radio interference. If radio
interference occurs, the user may be required to take appropriate
measures.
S8BA-LF
1 year from the date
of purchase and
afterward
1.5 years from the
date of purchase and
afterward
3 years from the date
of purchase and
afterward
6 years from the date
of purchase and
afterward