Omron S8BA LF Series Manual page 14

Uninterruptible power supply (ups), integrated battery type
Table of Contents

Advertisement

S8BA-LF
Do not exceed the ranges specified for environmental
conditions during use/storage.
Do not install or store the unit in the places listed below.
• Do not store in places where the humidity is lower than
10% or higher than 90%.
• Do not use the unit in places where the ambient
temperature is lower than 0°C or higher than 55°C.
(With no condensation)
• Do not use in places where the humidity is lower than
10% or higher than 90%.
• Do not install/store the unit in closed places such as
cabinets with no clearance, places where there is
flammable or corrosive gas,
• Places with large amounts of dust, places exposed to
direct sunlight, places exposed to shock or vibration,
salty or wet places, or outdoors.
• Installation or storing the unit in such a place may
cause a fire.
When you use plug strip and other plugs to connect
additional devices, do not connect devices that exceed
the current capacity of the available plugs.
• The current protection of the unit may operate, which
may stop the output.
• The cable heats up, which may cause a fire.
Do not pinch or sharply bend the cable.
Do not fold or knot the cable.
• Doing so may cause the cable to be damaged or
heated, which may cause an electric shock or a fire.
• If the cable is damaged, stop using the unit and have
the cable repaired.
• For details on repair, contact our sales personnel.
Connect only devices using 24 VDC rated voltage.
• The rated output voltage of the UPS is 24 VDC.
• Overvoltage or overcurrent may damage the
connected devices.
All the accessories contained in the product package can
be used for the UPS only. Do not use any of them for
other devices.
• Be sure to observe this to use the UPS safely.
Include a breaker between the "input power supply" of the
UPS and the direct power supply equipment. And, install
the breaker where it is easy to operate.
To use this product as a CE marking compliant device,
use a 2-meter or shorter connection cable.
Do not block the air vents (upper and lower).
• Doing so will cause the internal temperature to rise,
which may cause the unit to fail and the battery to
deteriorate.
• For stationary installation, leave a space of 50 mm or
more above the top, and for installation using a DIN rail
and screw clamps, leave a space of 50 mm or more
above the top and below the bottom each.
Do not connect the RS-232C port or the CONTACT port
to a LAN device using a LAN cable.
• Connection to a LAN device may result in malfunction
in or damage to the UPS or the LAN device.
14
(for use)
Do not allow the unit to come in contact with water. If you
drop the unit, stop using it.
• Doing so may cause an electric shock or a fire.
• Doing so may cause an abnormal heating, smoke,
rupture, or fire on the battery.
• If the unit becomes wet or is dropped, immediately
stop using it, disconnect the input power supply from
the wall outlet (commercial power source) and have it
inspected and repaired.
• For details on repair, contact our sales personnel.
When the battery is dead, replace it immediately or stop
using the unit.
• Continuing the use of it may cause fire or electric
shock due to liquid leaks.
Ambient temperature
Expected life
50°C
2.5 years
40°C
5 years
25°C
10 years
* The values in the table are the expected life under
standard use conditions and are not guaranteed.
Occasionally, wipe off dust on the input terminal block
and the output terminal block with a dry cloth.
• Accumulated dust may cause a fire.
• Before wiping off dust, stop all connected devices and
the unit, and stop the supply of commercial power.
Do not use the unit in a closed place and do not cover the
unit.
• Doing so may cause abnormal heating or a fire.
If you notice something unusual such as abnormal sound
or smell, discoloration, deformation, and heating, turn
OFF the unit's "Power" switch to stop the output and stop
the supply from the "input power supply".
• Using the unit under such conditions may cause an
abnormal heating, rupture or fire.
• If this situation arises, be sure to stop using the UPS
and request our sales personnel for inspection and
repair.
• A readily accessible disconnect device shall be
incorporated external to the equipment.
If fluid leaks from the interior, do not touch the fluid.
• Doing so may cause blindness or burns.
• If the fluid contacts your eyes or skin, wash it out with
lots of clean water and consult your doctor. The fluid
may damage your eye if your eye is left untreated.
Do not place any objects on the unit, and do not drop
heavy objects onto the unit.
• Doing so may cause distortion/damage to the case or
a failure of the internal circuit, which may cause a fire.
The unit is equipped with a bypass circuit which is able to
supply electric power to connected devices even when
the inner control circuit is broken down by defects or
malfunctions.
If you want to stop the output, stop the source of the "input
power supply".
• Output is continuing even when all indicators of the
front panel are off.
• Output ON/OFF cannot be controlled with the "Power"
switch on the front panel.
When charging the battery, if the battery cannot be
charged completely even after the predetermined
charging time, turn OFF the "Power" switch of the unit to
stop charging the battery.
• Otherwise, it may cause an abnormal heating, smoke,
rupture or fire on the battery.