Air Handlers - Lennox T-CLASS TS Series Engineering Data

Split system units
Table of Contents

Advertisement

RATINGS
NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
COOLING CAPACITY − TSA072S4S with
Total
85_F (29_C)
Entering
Air
Total
Wet Bulb
Volume
Comp
Cooling
Tempera-
Motor
Capacity
ture
kW
Input
cfm
L/s kBtuh kW
1920
905
69.1
20.3
4.83
63_F
2400 1135
72.6
21.3
4.86
(17_C)
2880 1360 75.7
22.2
4.87
1920
905
72.7
21.3
4.86
67_F
2400 1135
76.3
22.4
4.88
(19_C)
2880 1360 79.0
23.2
4.90
1920
905
76.3
22.4
4.88
71_F
2400 1135
80.0
23.4
4.90
(22_C)
2880 1360 82.7
24.2
4.91
COOLING CAPACITY − TSA072S4S with
Total
85_F (29_C)
Entering
Air
Total
Wet Bulb
Volume
Comp
Cooling
Tempera-
Motor
Capacity
ture
kW
Input
cfm
L/s kBtuh kW
1920
905
69.2
20.3
4.84
63_F
2400 1135
72.5
21.2
4.85
(17_C)
2880 1360 75.0
22.0
4.87
1920
905
73.0
21.4
4.86
67_F
2400 1135
76.2
22.3
4.88
(19_C)
2880 1360 78.8
23.1
4.90
1920
905
76.8
22.5
4.88
71_F
2400 1135
80.3
23.5
4.91
(22_C)
2880 1360 82.8
24.3
4.92
COOLING CAPACITY − TSA072S4S with
Total
85_F (29_C)
Entering
Air
Total
Wet Bulb
Volume
Comp
Cooling
Tempera-
Motor
Capacity
ture
kW
Input
cfm
L/s kBtuh kW
1920
905
70.4
20.6
4.84
63_F
2400 1135
74.0
21.7
4.87
(17_C)
2880 1360 76.7
22.5
4.88
1920
905
74.2
21.7
4.86
67_F
2400 1135
77.7
22.8
4.89
(19_C)
2880 1360 80.4
23.6
4.90
1920
905
78.4
23.0
4.89
71_F
2400 1135
81.9
24.0
4.92
(22_C)
2880 1360 84.3
24.7
4.93
TS 6 to 20 Ton R−410A Air Conditioners / Page 16
Outdoor Air Temperature Entering Outdoor Coil
95_F (35_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.68
.83
.98
66.2
19.4
5.37
.73
.91
1.00
69.5
20.4
5.40
.78
.97
1.00
72.6
21.3
5.42
.55
.66
.79
69.7
20.4
5.39
.57
.70
.87
72.9
21.4
5.41
.60
.75
.94
75.4
22.1
5.43
.41
.53
.64
73.0
21.4
5.42
.42
.56
.68
76.4
22.4
5.44
.44
.59
.73
79.1
23.2
5.46
Outdoor Air Temperature Entering Outdoor Coil
95_F (35_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.68
.82
.97
66.0
19.3
5.37
.72
.90
1.00
69.1
20.3
5.40
.77
.96
1.00
71.6
21.0
5.41
.54
.65
.78
69.7
20.4
5.40
.56
.69
.86
72.6
21.3
5.41
.59
.74
.93
75.2
22.0
5.43
.41
.52
.63
73.5
21.5
5.42
.42
.55
.67
76.7
22.5
5.44
.43
.57
.71
78.9
23.1
5.46
Outdoor Air Temperature Entering Outdoor Coil
95_F (35_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.68
.83
.99
67.2
19.7
5.38
.73
.92
1.00
70.5
20.7
5.40
.78
.99
1.00
72.9
21.4
5.41
.54
.66
.79
70.9
20.8
5.41
.57
.70
.87
74.1
21.7
5.43
.59
.75
.95
76.7
22.5
5.45
.41
.53
.64
74.9
22.0
5.43
.42
.56
.68
78.1
22.9
5.45
.43
.58
.73
80.4
23.6
5.47
105_F (41_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.70
.86
1.00
62.8
18.4
5.97
.75
.94
1.00
66.2
19.4
6.00
.80
1.00
1.00
68.9
20.2
6.01
.55
.67
.81
66.1
19.4
5.99
.58
.72
.90
69.2
20.3
6.03
.61
.78
.97
71.5
21.0
6.04
.42
.54
.65
69.5
20.4
6.02
.43
.57
.70
72.7
21.3
6.05
.44
.60
.75
75.0
22.0
6.07
105_F (41_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.69
.85
.99
62.5
18.3
5.97
.74
.93
1.00
65.5
19.2
6.00
.79
.98
1.00
67.8
19.9
6.01
.55
.67
.80
66.0
19.3
6.00
.57
.71
.88
68.9
20.2
6.02
.60
.76
.95
71.2
20.9
6.04
.42
.53
.64
69.7
20.4
6.03
.43
.56
.69
72.7
21.3
6.05
.44
.59
.73
74.8
21.9
6.07
105_F (41_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.69
.86
1.00
63.7
18.7
5.98
.75
.95
1.00
66.9
19.6
6.01
.80
1.00
1.00
69.4
20.3
6.02
.55
.67
.81
67.0
19.6
6.01
.58
.72
.90
70.3
20.6
6.03
.61
.78
.98
72.5
21.2
6.05
.41
.53
.65
71.1
20.8
6.04
.43
.56
.70
73.9
21.7
6.06
.44
.59
.75
76.1
22.3
6.08

AIR HANDLERS

[CBX27UH−060]
115_F (46_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.71
.89
1.00
59.1
17.3
6.66
.77
.97
1.00
62.4
18.3
6.69
.84
1.00
1.00
65.3
19.1
6.71
.56
.69
.84
62.3
18.3
6.69
.59
.75
.93
65.0
19.0
6.71
.62
.81
1.00
67.2
19.7
6.74
.42
.55
.67
65.4
19.2
6.71
.44
.58
.72
68.3
20.0
6.74
.45
.61
.78
70.5
20.7
6.77
115_F (46_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.70
.87
1.00
58.7
17.2
6.65
.76
.96
1.00
61.5
18.0
6.68
.82
1.00
1.00
63.8
18.7
6.70
.55
.68
.83
61.9
18.1
6.69
.58
.73
.92
64.7
19.0
6.70
.61
.79
.98
66.7
19.5
6.73
.42
.54
.66
65.5
19.2
6.71
.43
.57
.70
68.2
20.0
6.74
.44
.60
.76
70.1
20.5
6.76
115_F (46_C)
Sensible To Total
Total
Comp
Ratio (S/T)
Cooling
Motor
Dry Bulb
Capacity
kW
75_F
80_F
85_F
Input
kBtuh kW
24_C
27_C
29_C
.71
.89
1.00
59.7
17.5
6.67
.77
.98
1.00
62.6
18.3
6.69
.84
1.00
1.00
65.7
19.3
6.72
.56
.69
.84
63.1
18.5
6.70
.59
.74
.94
65.9
19.3
6.72
.62
.81
1.00
68.0
19.9
6.74
.42
.55
.66
66.6
19.5
6.72
.43
.58
.72
69.4
20.3
6.75
.45
.61
.78
71.4
20.9
6.77
6 TON
Sensible To Total
Ratio (S/T)
Dry Bulb
75_F
80_F
85_F
24_C
27_C
29_C
.74
.93
1.00
.80
1.00
1.00
.88
1.00
1.00
.57
.71
.88
.61
.78
.97
.64
.85
1.00
.42
.56
.69
.44
.60
.75
.46
.63
.82
[CBX32M−060]
Sensible To Total
Ratio (S/T)
Dry Bulb
75_F
80_F
85_F
24_C
27_C
29_C
.72
.91
1.00
.79
.98
1.00
.85
1.00
1.00
.56
.70
.87
.60
.76
.95
.62
.82
1.00
.42
.55
.68
.44
.58
.73
.45
.62
.79
[TAA072S4S]
Sensible To Total
Ratio (S/T)
Dry Bulb
75_F
80_F
85_F
24_C
27_C
29_C
.73
.93
1.00
.80
1.00
1.00
.87
1.00
1.00
.57
.71
.88
.60
.77
.98
.63
.84
1.00
.42
.55
.68
.44
.59
.74
.45
.62
.81

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents