[8-14 Hydro Unit Maintenance Instructions ]
8-14-2
Strainer Replacement Procedure
Operation procedures
1) Remove all refrigerant from the pipes.
2) Remove the front panel (8 screws).
3) Remove the saddle by unscrewing the
screws.
4) Remove the braze from the areas circled in
the figure.
5) Pull the pipe out in the direction of the ar-
row.
6) Remove the strainer from the pipe, and re-
place it.
122
- chapter 8
(2)
(3)
Strainer
(4)
Illustrations
Service panel (front)
Saddle
(5)
(5)
Strainer
BS_08_E