General Overview On Lev Operation (Hydro Unit) - Mitsubishi Electric PUHY-M200YNW-A1 Service Handbook

Table of Contents

Advertisement

[8-8 Troubleshooting LEV, FCV Problems ]
8-8-2

General Overview on LEV Operation (Hydro unit)

LEV operation
Hydro unit LEV1 (linear expansion valves) is driven by the pulse signal from the control board and are controlled by a stepping
motor.
(1) Hydro unit LEV
The valve opening changes according to the number of pulses.
1) Control boards and the LEV (Hydro unit LEV1)
LEV
Blue
4
Red
6
M
Yellow
2
5
1
White
Orange
2) Pulse signal output and valve operation
Output
(phase)
number
1
1
ON
2
ON
3
OFF
4
OFF
BS_08_E
ø4
ø3
ø2
ø1
Output state
2
3
4
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
Control board
6
Brown
5
Blue
4
Orange
3
Yellow
2
1
White
Output pulses change in the following orders when the
Valve is closed; 1
2
Valve is open;
4
3
*1. When the LEV opening angle does not change,
all the output phases will be off.
*2. When the output is open phase or remains ON,
the motor cannot run smoothly, and rattles and vibrates.
DC12V
Drive circuit
ø4
ø3
ø2
ø1
3
4
1
2
1
4
chapter 8 -
27

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents