Maximum Refrigerant Charge - Mitsubishi Electric PUHY-M200YNW-A1 Service Handbook

Table of Contents

Advertisement

[6-3 Evaluating and Adjusting Refrigerant Charge ]
6-3-3

Maximum refrigerant charge

There is a limit to the amount of refrigerant that can be charged into a unit. Observe the maximum refrigerant charge in the
table below.
M200-500YNW-A1
Total index of the outdoor units
Factory charge (kg)
Maximum additional refrigerant
charge on site (kg)
Maximum refrigerant charge (kg)
EM200-500YNW-A1
Total index of the outdoor units
Factory charge (kg)
Maximum additional refrigerant
charge on site (kg)
Maximum refrigerant charge (kg)
BS_06_E
M200
M250
M300
6.5
6.5
6.5
8.5
8.5
8.5
15.0
15.0
15.0
EM200
EM250
EM300
6.5
6.5
6.5
8.5
8.5
8.5
15.0
15.0
15.0
M350
M400
M450
9.8
9.8
10.8
14.0
14.0
19.0
23.8
23.8
29.8
EM350
EM400
EM450
9.8
10.8
10.8
14.0
15.0
19.0
23.8
29.8
29.8
M500
10.8
19.0
29.8
EM500
10.8
19.0
29.8
3
chapter 6 -