[8-10 Troubleshooting Inverter Problems ]
Items to be checked
<INV37YC>
BS_08_E
Phenomena
3)
An overcurrent error occurs during oper-
ation.
Error code : 4250
Detail code : 121,122
4)
An overcurrent error occurs immediately
after compressor startup.
Error code : 4250
Detail code :101,106,107,128
5)
An overvoltage error occurs during oper-
ation.
Error code : 4220
Detail code :109,110,112
6)
No problems were found with items 1)
through 5).
Remedy
[8-10-6 Checking the Converter for
Damage during Compressor Oper-
ation]
a.
Check for refrigerant flooding.
→When the problem persists after
compressor startup was repeated
several times, go to "d" after a cer-
tain time after energizing the com-
pressor or the heater.
If normal operation is restored,
check the belt heater for problems.
b.
Check that there is a pressure dif-
ference between high and low
pressures after compressor start-
up.
→Check the high pressure with
LED monitor for changes.
Replace the compressor if there is
no pressure difference. (the com-
pressor may be locked.)
c.
Check for interphase voltage im-
balance.
d.
Replace the INV board if no prob-
lems were found with the items a or
c.
e.
If the problem persists after replac-
ing the inverter board, [8-10-3
Checking the Compressor for
Ground Fault and Coil Resistance
Problems]
[8-10-6 Checking the Converter for
Damage during Compressor Oper-
ation]
Normal [8-10-6 Checking the Con-
verter for Damage during Com-
pressor Operation]
45
chapter 8 -